Inspections for the day of: Thursday, December 30, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00235 FIR-Aging Inspection12/30/201012/30/20101/7/2011 3:15:22 PM NR
Trent is calling for a final on monday.
FIR10-00327 FIR-Aging Inspection12/30/201012/30/20101/7/2011 2:32:19 PM CANC
Project has been voided
BLD10-00114 FIRE-Conference12/30/201012/30/20101/3/2011 3:06:29 PMADONE
Does 8.15.7.3 apply to small extension of the new front entrance as suggested by fire sprinkler subcontractor
Information was forwarded to Tim Frost who agreed this section of code could be applied but the combustible spaces would either have to have sprinkler protection or be filled with non combustible insulation.
BLD10-00851 BLD-Aging Inspection12/30/201012/30/20101/3/2011 11:25:13 AMPCANC
Called in for a final inspection for 1-3-2011
BLD10-02720 FIRE-Final Inspection12/30/201012/30/201012/30/2010 3:15:21 PMPPASS
Life safety passed
FIR10-00615 INSP-Final Inspection12/30/201012/30/201012/30/2010 3:05:55 PMPPASS
Permit finaled
BLD10-02912 FIRE-Final Inspection12/29/201012/30/201012/30/2010 2:54:04 PMAPASS
life safety passed
FIR10-00643 INSP-Sprinkler Rough-in12/29/201012/30/201012/30/2010 12:25:27 PMAPASS
Sprinkler piping can be covered.
FIR10-00500 INSP-Final Inspection12/29/201012/30/201012/30/2010 12:24:36 PMAPASS
Permit finaled
FIR10-00548 INSP-Final Inspection12/28/201012/30/201012/30/2010 12:24:03 PMAFAIL
Many of the strobes are overspaced. Visual coverage is required in the Janitors closet since it is now a part of the common area due to the door not being installed. The PIV valve label at the remote annunciator needs to be labeled correctly. It is currently labeled "anti-freeze". The notification circuit was not activated for testing due to the outstanding issues. A drawing plan modification will be required to be submitted for approval if additional devices are added or candella modified.
BLD10-02911 FIRE-Final Inspection12/29/201012/30/201012/30/2010 12:09:23 PMAPASS
life safety passed