ELE13-03337
| Final | 12/30/2013 | 12/30/2013 | 12/30/2013 3:07:19 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jerry Moore final ok
|
ELE13-03565
| Rough-In Permanent Service | 12/30/2013 | 12/30/2013 | 12/30/2013 2:40:36 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC 210.52 (A)(1) receptacle spacing, receptacle required under breakfast bar. Branch circuits ran through bored holes, NEC only allows up to three NM cable per hole for heat disapation
|
GCE13-00207
| GCE-Rough-In | 12/30/2013 | 12/30/2013 | 12/30/2013 1:44:23 PM | P | NR |
|
|
Butch ###-#### Not ready
|
ELE13-03066
| Electrical Rough-In | 12/29/2013 | 12/30/2013 | 12/30/2013 12:55:07 PM | A | FAIL |
|
|
ceiling cover 2nd floor and basement Phone #: ###-#### >> Inspection requested via web by Karl Paige Basement level NEC 800.25 The accessible portionof abandoned communnication cables shall be removed. Support MC cables off grid. Support j-boxes in hallway
|
ELE13-03066
| Electrical Rough-In | 12/30/2013 | 12/30/2013 | 12/30/2013 12:49:23 PM | P | PASS |
|
|
ceiling cover 2nd floor Phone #: ###-#### >> Inspection requested via web by Karl Paige rough-in ok cover ceiling grid
|
ELE13-02430
| Electrical Rough-In | 12/27/2013 | 12/30/2013 | 12/30/2013 10:15:55 AM | A | PASS |
|
|
Re-inspection of grid. Contact is Nathan Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery correction done, rough-in ok cover
|
GCE13-00207
| GCE-Rough-In | 12/27/2013 | 12/30/2013 | 12/30/2013 9:54:43 AM | A | PASS |
|
|
Butch ###-#### ceiling rough-in ok cover hard lid bathrooms, hallway
|
ELE13-03485
| Conference | 12/27/2013 | 12/30/2013 | 12/30/2013 9:26:49 AM | A | DONE |
|
|
ken - call 30 mins prior Phone #: ###-#### Discussed with homeowner electrical requirements for wiring detached garage/shop
|
ELE13-02923
| Final | 12/29/2013 | 12/30/2013 | 12/30/2013 8:57:03 AM | A | PASS |
|
|
Call me if house is locked, I will give you garage code. Thanks Daryl! Phone #: ###-#### >> Inspection requested via web by Julie Schroder final ok
|
ELE13-03428
| Rough-In Permanent Service | 12/27/2013 | 12/30/2013 | 12/30/2013 8:32:25 AM | A | PASS |
|
|
Contact person Jim Snodgrass Phone #: ###-#### >> Inspection requested via web by Todd Sellman rough-in p/s u/g rec ok
|