ELE14-03260
| Electrical Rough-In | 12/30/2014 | 12/30/2014 | 12/30/2014 2:27:30 PM | P | PART |
|
|
Underground Inspection - Contact is Ryan Weidrich ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell u/g ne of shelter runnng diagonally to se ok cover
|
ELE14-03556
| Permanent Service | 12/30/2014 | 12/30/2014 | 12/30/2014 12:30:56 PM | P | PASS |
|
|
owners should be home and house un locked meter main out back and panel in basement. Please call with any questions Phone #: ###-#### Inspection requested via web by Brad Baker p/s o/h rec ok, NOTE: check grounding, nail plates over panel, strapping riser,4-wire for range and dryer, work space about main service, labelling at final
|
ELE12-02003
| ELE-Aging Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 11:25:10 AM | | DONE |
|
|
called to set up final
|
ELE14-03423
| Electrical Rough-In | 12/30/2014 | 12/30/2014 | 12/30/2014 11:08:02 AM | P | CANC |
|
|
ok they should have it cleaned up now thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig Inspection cancelled from web by: Don Lustig
|
ELE12-01952
| ELE-Aging Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 10:41:07 AM | | DONE |
|
|
called to set up final
|
ELE14-03540
| Rough-In Permanent Service | 12/29/2014 | 12/30/2014 | 12/30/2014 10:27:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas ri ok, p/s u/g n ok
|
ELE14-03541
| Rough-In Permanent Service | 12/29/2014 | 12/30/2014 | 12/30/2014 9:39:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas ri ok, p/s u/g n ok
|
ELE14-03074
| Final | 12/29/2014 | 12/30/2014 | 12/30/2014 8:46:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher ok final
|
ELE14-03423
| Electrical Rough-In | 12/29/2014 | 12/30/2014 | 12/30/2014 8:25:16 AM | A | FAIL |
|
|
ceiling cover inspection call steve if needed he should be on site Phone #: ###-#### Inspection requested via web by Don Lustig ceiling covered, opened some tile, low voltage not removed, laying on grid, seismic wires missing, told to open up and recall
|
ELE14-02762
| Electrical Rough-In | 12/29/2014 | 12/30/2014 | 12/30/2014 4:41:11 AM | A | CANC |
|
|
Underground inspection in front lobby; (3) sawcuts ; floor boxes. Phone #: ###-#### Inspection requested via web by Steve McCloy see 4-29-14 inspection, this is duplicate request
|
ELE14-03544
| Rough-In Permanent Service | 12/29/2014 | 12/30/2014 | 12/29/2014 12:33:52 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by kevin blackmon Inspection cancelled from web by: kevin blackmon
|