BLD14-02366
| FIRE-Final Inspection | 12/29/2014 | 12/30/2014 | 12/30/2014 3:32:21 PM | P | PASS |
|
|
life safety passed. No hardware on door.
|
FIR14-00926
| INSP-Final Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 3:21:56 PM | P | FAIL |
|
|
No testing performed due to no water for fire sprinkler testing and it appears the backflow tamper switch may be wired incorrectly
|
FIR14-00554
| INSP-Final Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 3:21:07 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00449
| INSP-Final Inspection | 12/29/2014 | 12/30/2014 | 12/30/2014 3:19:38 PM | P | FAIL |
|
|
Provide plan modification showing all of the duct smoke detectors including the in-duct detectors and the remoter power supply on the second floor, provide verification the in-duct detectors are with-in their velocity listing for use in the HVAC units, provide verification the smoke detector at the second floor/north stairs is approved to be located outside of code requirements (detector is not shown on plans), install the heat detectors as shown on the approved plans or get approval to delete.
|
FIR14-00556
| INSP-Final Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 2:56:10 PM | P | FAIL |
|
|
no water, no inspection
|
FIR14-00821
| INSP-Final Inspection | 12/30/2014 | 12/30/2014 | 12/30/2014 12:26:56 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00745
| INSP-Sprinkler Rough-in | 12/29/2014 | 12/30/2014 | 12/30/2014 12:22:21 PM | A | PASS |
|
|
6" main needs to be installed/inspected and the tie-in's to the existing system. Outside canopy is ok to cover. Need sprinkler coverage installed under doors.
|
BLD14-03417
| FIRE-Final Inspection | 12/29/2014 | 12/30/2014 | 12/30/2014 10:20:41 AM | A | PASS |
|
|
life safety passed
|