Inspections for the day of: Tuesday, December 30, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-02366 FIRE-Final Inspection12/29/201412/30/201412/30/2014 3:32:21 PMPPASS
life safety passed. No hardware on door.
FIR14-00926 INSP-Final Inspection12/30/201412/30/201412/30/2014 3:21:56 PMPFAIL
No testing performed due to no water for fire sprinkler testing and it appears the backflow tamper switch may be wired incorrectly
FIR14-00554 INSP-Final Inspection12/30/201412/30/201412/30/2014 3:21:07 PMPPASS
Permit finaled
FIR14-00449 INSP-Final Inspection12/29/201412/30/201412/30/2014 3:19:38 PMPFAIL
Provide plan modification showing all of the duct smoke detectors including the in-duct detectors and the remoter power supply on the second floor, provide verification the in-duct detectors are with-in their velocity listing for use in the HVAC units, provide verification the smoke detector at the second floor/north stairs is approved to be located outside of code requirements (detector is not shown on plans), install the heat detectors as shown on the approved plans or get approval to delete.
FIR14-00556 INSP-Final Inspection12/30/201412/30/201412/30/2014 2:56:10 PMPFAIL
no water, no inspection
FIR14-00821 INSP-Final Inspection12/30/201412/30/201412/30/2014 12:26:56 PMPPASS
Permit finaled
FIR14-00745 INSP-Sprinkler Rough-in12/29/201412/30/201412/30/2014 12:22:21 PMAPASS
6" main needs to be installed/inspected and the tie-in's to the existing system. Outside canopy is ok to cover. Need sprinkler coverage installed under doors.
BLD14-03417 FIRE-Final Inspection12/29/201412/30/201412/30/2014 10:20:41 AMAPASS
life safety passed