Inspections for the day of: Wednesday, December 30, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03936 Permanent Service12/30/201512/30/201512/30/2015 2:26:12 PMPFAIL
Phone #: ###-#### Inspection requested via web by kendall bender
110.9- Equipment intended to interupt current at fault levels shall have an interupting rating sufficient for fault current available at line terminals. 13,283 available fault current on 10,000 rated main breaker.
ELE15-03489 Electrical Rough-In12/29/201512/30/201512/30/2015 2:03:07 PMPPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Wall rough in ok cover
ELE15-04120 Electrical Rough-In12/30/201512/30/201512/30/2015 1:20:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Schroeder
Kitchen layout staying same with addition of receptacles to serve counter top to todays code. Rough in ok cover
ELE15-03117 Electrical Rough-In12/30/201512/30/201512/30/2015 12:42:14 PMPCANC
service inspection, Greg Milburn is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Needed permanent service inspection
ELE15-03117 Permanent Service12/30/201512/30/201512/30/2015 12:41:47 PMPPASS
service inspection, Greg Milburn is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce p/s u/g n ok
ELE15-04130 Electrical Rough-In12/30/201512/30/201512/30/2015 10:45:24 AMAPASS
Phone #: ###-#### Inspection requested via web by John VanZandt Kitchen and M. bath rough in ok cover
ELE15-03386 Final12/29/201512/30/201512/30/2015 10:04:06 AMAPASS
Call for access code
Thanks, Greg Phone #: ###-#### Inspection requested via web by Greg Idsinga Final ok
ELE15-03764 Final12/28/201512/30/201512/30/2015 9:42:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by cris flores
210.8- All 120 volt receptacle outlets located within 6' of sinks shall have GFCI protection.
Bath GFCI dead and outlet in laundry area not working.
ELE15-03764 Electrical Rough-In12/30/201512/30/201512/30/2015 9:27:58 AMPPASS
Phone #: ###-#### Inspection requested via web by cris flores
Grid rough in ok cover
ELE15-03599 Final12/29/201512/30/201512/30/2015 9:09:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE15-04080 Rough-In Permanent Service12/29/201512/30/201512/30/2015 8:47:05 AMAPASS
Phone #: ###-#### Inspection requested via web by cal crosby Rough in ok cover p/s u/g n ok