ELE12-01237
| ELE-Aging Inspection | 12/30/2015 | 12/30/2015 | 12/31/2015 9:55:23 AM | | DONE |
|
|
spoke with secratary and she will get Gary to call this in
|
ELE11-01053
| ELE-Aging Inspection | 12/30/2015 | 12/30/2015 | 12/31/2015 9:54:34 AM | | DONE |
|
|
spoke with secratary and she will get Gary to call this in
|
ELE15-03707
| Final | 12/30/2015 | 12/30/2015 | 12/30/2015 2:40:27 PM | P | FAIL |
|
|
Tim-please call 1 hr prior to meet for access Phone #: ###-#### Boise ordinance 4-05-32-no code violations shall be retained. 210.8 (B)(1)- all 120 volt receptacles in bathrooms in other than dwellings shall be GFCI protected. 210.8(B)(2) and (5) all 120 volt receptacles in kitchnens in other than dwellings shall have GFCI protection within 6 foot of sinks. 110.16- arc flash label on loadcenters required. Update panel schedule. Install receptacle covers on floor boxes.
|
ELE15-03943
| Final | 12/29/2015 | 12/30/2015 | 12/30/2015 2:04:53 PM | P | PART |
|
|
We are requesting a final inspection for tomorrow 12/30/15 in the afternoon. Our contact is Bryant @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate partial final ok need to see office furniture after connected and arc flash stickers on loadcenters
|
ELE15-04082
| Rough-In Permanent Service | 12/30/2015 | 12/30/2015 | 12/30/2015 1:29:47 PM | P | PASS |
|
|
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok p/s o/h n ok
|
GCE15-00177
| GCE-Rough-In Permanent Service | 12/30/2015 | 12/30/2015 | 12/30/2015 12:41:51 PM | P | PASS |
|
|
Brandon ###-#### r/i ok p/s u/g n ok
|
ELE15-04086
| Conference | 12/29/2015 | 12/30/2015 | 12/30/2015 10:08:33 AM | A | DONE |
|
|
Chistian Phone #: ###-#### discuss wiring for new bathroom. Suggested running new 20 amp circuit to feed all electrical in bathroom and safe off existing wiring and call for r/i insp. prior to covering
|
ELE15-04122
| Electrical Rough-In | 12/29/2015 | 12/30/2015 | 12/30/2015 9:37:24 AM | A | PASS |
|
|
Need wall rough-in inspection - Field Electrician Joel Hudson Cell ####-#### Phone #: Inspection requested via web by Kevin Perez r/i walls ok
|
ELE15-03525
| Electrical Rough-In | 12/29/2015 | 12/30/2015 | 12/30/2015 8:51:53 AM | A | PASS |
|
|
we are requesting a ceiling rough-in inspection in the front counter area tomorrow morning. our contact is Luke @ ###-####. thank you Phone #: ###-#### Inspection requested via web by Clint Tate r/i t grid ceilings in POS area ok
|
ELE15-03152
| Final | 12/29/2015 | 12/30/2015 | 12/30/2015 8:23:07 AM | A | PASS |
|
|
Access code for garage 5050 + enter Phone #: ###-#### Inspection requested via web by HZ ZAHIC final ok
|
ELE15-03525
| Electrical Rough-In | 12/29/2015 | 12/30/2015 | 12/29/2015 5:43:24 PM | P | CANC |
|
|
We are requesting a ceiling rough-in inspection for the front counter area for tomorrow 12/30/15. Our contact is Luke @ ###-####. Thank you! Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|