Inspections for the day of: Wednesday, December 30, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01237 ELE-Aging Inspection12/30/201512/30/201512/31/2015 9:55:23 AM DONE
spoke with secratary and she will get Gary to call this in
ELE11-01053 ELE-Aging Inspection12/30/201512/30/201512/31/2015 9:54:34 AM DONE
spoke with secratary and she will get Gary to call this in
ELE15-03707 Final12/30/201512/30/201512/30/2015 2:40:27 PMPFAIL
Tim-please call 1 hr prior to meet for access Phone #: ###-#### Boise ordinance 4-05-32-no code violations shall be retained. 210.8 (B)(1)- all 120 volt receptacles in bathrooms in other than dwellings shall be GFCI protected. 210.8(B)(2) and (5) all 120 volt receptacles in kitchnens in other than dwellings shall have GFCI protection within 6 foot of sinks. 110.16- arc flash label on loadcenters required. Update panel schedule. Install receptacle covers on floor boxes.
ELE15-03943 Final12/29/201512/30/201512/30/2015 2:04:53 PMPPART
We are requesting a final inspection for tomorrow 12/30/15 in the afternoon. Our contact is Bryant @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate partial final ok need to see office furniture after connected and arc flash stickers on loadcenters
ELE15-04082 Rough-In Permanent Service12/30/201512/30/201512/30/2015 1:29:47 PMPPASS
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok p/s o/h n ok
GCE15-00177 GCE-Rough-In Permanent Service12/30/201512/30/201512/30/2015 12:41:51 PMPPASS
Brandon ###-#### r/i ok p/s u/g n ok
ELE15-04086 Conference12/29/201512/30/201512/30/2015 10:08:33 AMADONE
Chistian Phone #: ###-#### discuss wiring for new bathroom. Suggested running new 20 amp circuit to feed all electrical in bathroom and safe off existing wiring and call for r/i insp. prior to covering
ELE15-04122 Electrical Rough-In12/29/201512/30/201512/30/2015 9:37:24 AMAPASS
Need wall rough-in inspection - Field Electrician Joel Hudson Cell ####-#### Phone #: Inspection requested via web by Kevin Perez r/i walls ok
ELE15-03525 Electrical Rough-In12/29/201512/30/201512/30/2015 8:51:53 AMAPASS
we are requesting a ceiling rough-in inspection in the front counter area tomorrow morning. our contact is Luke @ ###-####. thank you Phone #: ###-#### Inspection requested via web by Clint Tate r/i t grid ceilings in POS area ok
ELE15-03152 Final12/29/201512/30/201512/30/2015 8:23:07 AMAPASS
Access code for garage 5050 + enter Phone #: ###-#### Inspection requested via web by HZ ZAHIC final ok
ELE15-03525 Electrical Rough-In12/29/201512/30/201512/29/2015 5:43:24 PMPCANC
We are requesting a ceiling rough-in inspection for the front counter area for tomorrow 12/30/15. Our contact is Luke @ ###-####. Thank you! Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate