ELE16-04156
| Temporary Service | 12/29/2016 | 12/30/2016 | 12/30/2016 10:54:33 AM | A | PASS |
|
|
The on-site office will have the key for you, if you have any electrical questions, please call Luke at ###-####. If you have any issues getting access, please call Joe at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clay Morgan Energizing house panel to left of main disconnect for temporary power. Called contractor to ensure all sub feeds safed off. t/s u/g n ok
|
ELE16-02927
| Final | 12/29/2016 | 12/30/2016 | 12/30/2016 10:31:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Final ok
|
ELE16-03453
| Final | 12/29/2016 | 12/30/2016 | 12/30/2016 9:34:48 AM | A | FAIL |
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis 110.3- Devices shall be connected as per manufacturers instructions. Reverse polarity 2nd floor at top of stair. 110.25- A disconnecting means shall be provided for dishwasher and hood as per 422.30 lockout acceptable. 210.22- Receptacle rating shall not exceed branch circuit rating. 50 amp installed in dryer. 406.5- Dining receptacle shall be secured to box. 440.6- AC over current device shall not exceed that of nameplate rating. 30 amp installed on 25 amp max unit. posted notice and had verbal with wireman on site
|
ELE16-03525
| Final | 12/29/2016 | 12/30/2016 | 12/30/2016 9:23:57 AM | A | FAIL |
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis 110.25- Dishwasher shall have a disconnecting means as per 422.30 lock out acceptable. 440.6- AC overcurrent device shall not exceed nameplate rating. 30 amp on 25 amp max.
|