Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04156 Temporary Service12/29/201612/30/201612/30/2016 10:54:33 AMAPASS
The on-site office will have the key for you, if you have any electrical questions, please call Luke at ###-####. If you have any issues getting access, please call Joe at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clay Morgan
Energizing house panel to left of main disconnect for temporary power. Called contractor to ensure all sub feeds safed off. t/s u/g n ok
ELE16-02927 Final12/29/201612/30/201612/30/2016 10:31:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Ben Archibald
Final ok
ELE16-03453 Final12/29/201612/30/201612/30/2016 9:34:48 AMAFAIL
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis
110.3- Devices shall be connected as per manufacturers instructions. Reverse polarity 2nd floor at top of stair.
110.25- A disconnecting means shall be provided for dishwasher and hood as per 422.30 lockout acceptable.
210.22- Receptacle rating shall not exceed branch circuit rating. 50 amp installed in dryer.
406.5- Dining receptacle shall be secured to box.
440.6- AC over current device shall not exceed that of nameplate rating. 30 amp installed on 25 amp max unit.
posted notice and had verbal with wireman on site
ELE16-03525 Final12/29/201612/30/201612/30/2016 9:23:57 AMAFAIL
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis
110.25- Dishwasher shall have a disconnecting means as per 422.30 lock out acceptable.
440.6- AC overcurrent device shall not exceed nameplate rating. 30 amp on 25 amp max.