Inspections for the day of: Friday, December 30, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00900 INSP-Final Inspection12/29/201612/30/201612/30/2016 1:33:33 PMPCANC
Final inspection for fire sprinklers will be rescheduled for a later date.
FIR16-00372 INSP-Final Inspection12/29/201612/30/201612/30/2016 12:41:38 PMPPASS
Final fire alarm inspection passed/complete.
FIR16-00594 INSP-Final Inspection12/29/201612/30/201612/30/2016 11:51:53 AMAFAIL
Audio visual devices tested and inspected, all tested correctly. On-site city approved drawings do not match the system installed, approved drawings show numerous smoke detectors throughout space and the smoke detectors have been reomved. A city approved drawing needs to be provided showing the removal of the devices or the system will need to match what was submitted.
FIR15-00900 INSP-Supply line flush12/29/201612/30/201612/30/2016 11:06:41 AMADONE
Underground supply flush complete.
FIR16-00510 INSP-Sprinkler Rough-in/Hydro12/29/201612/30/201612/30/2016 9:48:17 AMPCANC
Hydrostatic test cancelled by point of contact due to weather conditions.
FIR16-00086 INSP-Final Inspection12/30/201612/30/201612/30/2016 9:31:28 AMAPASS
Final inspection for clean agent fire panel interface to existing fire alarm panel passed/complete, permit finaled.
BLD16-02995 FIRE-Final Inspection12/30/201612/30/201612/30/2016 9:25:37 AMAPASS
Final fire sprinkler inspection complete (FIR permit was not attached to this project, fire sprinkler work completed under FIR16-00782), final fire alarm inspection complete, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
FIR16-00686 INSP-Final Inspection12/29/201612/30/201612/30/2016 9:23:02 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00818 INSP-Final Inspection12/29/201612/30/201612/30/2016 9:22:39 AMAPASS
Final fire alarm inspection for clean agent panel interface with building fire alarm panel passed/complete.
FIR16-00088 INSP-Sprinkler Rough-in12/29/201612/30/201612/30/2016 8:07:36 AMAFAIL
Overhead fire sprinkler piping on level 6 cannot be covered, every apartment on level 6 has piping that is completely covered with insulation, a clear pocket needs to be maintained between all overhead fire sprinkler piping and the sheetrock, tenting will need to be re-inspected
FIR16-00437 INSP-Final Inspection12/28/201612/30/201612/30/2016 12:00:00 AMACANC
Paul Phone #: ###-####