FIR15-00900
| INSP-Final Inspection | 12/29/2016 | 12/30/2016 | 12/30/2016 1:33:33 PM | P | CANC |
|
|
Final inspection for fire sprinklers will be rescheduled for a later date.
|
FIR16-00372
| INSP-Final Inspection | 12/29/2016 | 12/30/2016 | 12/30/2016 12:41:38 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR16-00594
| INSP-Final Inspection | 12/29/2016 | 12/30/2016 | 12/30/2016 11:51:53 AM | A | FAIL |
|
|
Audio visual devices tested and inspected, all tested correctly. On-site city approved drawings do not match the system installed, approved drawings show numerous smoke detectors throughout space and the smoke detectors have been reomved. A city approved drawing needs to be provided showing the removal of the devices or the system will need to match what was submitted.
|
FIR15-00900
| INSP-Supply line flush | 12/29/2016 | 12/30/2016 | 12/30/2016 11:06:41 AM | A | DONE |
|
|
Underground supply flush complete.
|
FIR16-00510
| INSP-Sprinkler Rough-in/Hydro | 12/29/2016 | 12/30/2016 | 12/30/2016 9:48:17 AM | P | CANC |
|
|
Hydrostatic test cancelled by point of contact due to weather conditions.
|
FIR16-00086
| INSP-Final Inspection | 12/30/2016 | 12/30/2016 | 12/30/2016 9:31:28 AM | A | PASS |
|
|
Final inspection for clean agent fire panel interface to existing fire alarm panel passed/complete, permit finaled.
|
BLD16-02995
| FIRE-Final Inspection | 12/30/2016 | 12/30/2016 | 12/30/2016 9:25:37 AM | A | PASS |
|
|
Final fire sprinkler inspection complete (FIR permit was not attached to this project, fire sprinkler work completed under FIR16-00782), final fire alarm inspection complete, fire extinguisher is in place with current inspection tag. Final life fire safety inspection passed/complete.
|
FIR16-00686
| INSP-Final Inspection | 12/29/2016 | 12/30/2016 | 12/30/2016 9:23:02 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00818
| INSP-Final Inspection | 12/29/2016 | 12/30/2016 | 12/30/2016 9:22:39 AM | A | PASS |
|
|
Final fire alarm inspection for clean agent panel interface with building fire alarm panel passed/complete.
|
FIR16-00088
| INSP-Sprinkler Rough-in | 12/29/2016 | 12/30/2016 | 12/30/2016 8:07:36 AM | A | FAIL |
|
|
Overhead fire sprinkler piping on level 6 cannot be covered, every apartment on level 6 has piping that is completely covered with insulation, a clear pocket needs to be maintained between all overhead fire sprinkler piping and the sheetrock, tenting will need to be re-inspected
|
FIR16-00437
| INSP-Final Inspection | 12/28/2016 | 12/30/2016 | 12/30/2016 12:00:00 AM | A | CANC |
|
|
Paul Phone #: ###-####
|