FIR19-00964
| INSP-Final Inspection | 12/30/2019 | 12/30/2019 | 12/30/2019 3:55:50 PM | P | PASS |
|
|
Final hood suppression system inspection is comlpete.
Phone #: ###-#### Inspection requested via web by Don Kartchner
|
FIR18-00858
| INSP-Final Inspection | 12/27/2019 | 12/30/2019 | 12/30/2019 3:52:54 PM | P | PART |
|
|
Walkthrough completed for remaining level 2 and basment level. Walkthrough not performed on level 1, base of A/V devices were masked for painting, could not see candella setting.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
BLD19-03277
| FIRE-Final Inspection | 12/30/2019 | 12/30/2019 | 12/30/2019 3:31:59 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, space is a vanilla finish so no fire extinguishers, final life fire safety inspection for vanilla TI complete, as stated in the project description, no occupancy allowed under this permit.
Matt Phone #: ###-####
|
BLD19-03521
| FIRE-Final Inspection | 12/30/2019 | 12/30/2019 | 12/30/2019 2:52:39 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.
Sid Phone #: ###-####
|
BLD19-02869
| FIRE-Final Inspection | 12/30/2019 | 12/30/2019 | 12/30/2019 2:36:36 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modificaitons, final life fire safety inspection for vanilla TI complete, signatures provided on permit sign off card. As noted it project description, no occupancy allowed under this permit.
Tom Phone #: ###-####
|
BLD19-04886
| FIRE-Final Inspection | 12/30/2019 | 12/30/2019 | 12/30/2019 12:52:30 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signature provided on permit sign off card.
Kim Phone #: ###-####
|
FIR19-00353
| INSP-Sprinkler Rough-in | 12/30/2019 | 12/30/2019 | 12/30/2019 11:51:16 AM | P | FAIL |
|
|
ADA room level 1 has open outlet above hard-lid, outlet is for sprinkler head in combustible concealed space behind bathtub, piping/head is not installed at time of inspection. Restraint clip for pendant fire sprinkler head in same ADA bathroom is not installed. Pipe size for electrical room (piping from double queen ext room, west of ADA room supplies electrical room) behind storage room shows 1 inch on city approved drawings, 1 1/2 pipe appears to be whats installed, not 1 inch as shown on drawings.
1st floor rooms drop ceilings. Thank you. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
BLD19-04340
| FIRE-Final Inspection | 12/27/2019 | 12/30/2019 | 12/30/2019 10:17:14 AM | A | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for scope of work complete.
Tom Phone #: ###-####
|
BLD19-03930
| FIRE-Conference | 12/27/2019 | 12/30/2019 | 12/30/2019 9:50:23 AM | A | DONE |
|
|
Fire conference complete.
Rick Phone #: ###-####
|
BLD19-01927
| FIRE-Conference | 12/24/2019 | 12/30/2019 | 12/30/2019 8:58:46 AM | A | DONE |
|
|
Fire conference complete.
Emergency light fixture layout, workstation furniture, additional signage requirements Phone #: ###-#### Inspection requested via web by Sam Reading
|
BLD19-03738
| FIRE-Final Inspection | 12/27/2019 | 12/30/2019 | 12/30/2019 8:33:58 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for scope of work complete, signature provided on permit sign off card.
Tom Phone #: ###-####
|