BLD08-01619
| BLD-Aging Inspection | 12/31/2008 | 12/31/2008 | 12/31/2008 5:28:09 PM | | DONE |
|
|
Final site inspection scheduled.
|
FIR08-00369
| INSP-Sprinkler Rough-in/Hydro | 12/30/2008 | 12/31/2008 | 12/31/2008 5:26:08 PM | P | FAIL |
|
|
Approved plan set on site does not match floorplan or actual installation including heads and piping beneath three mezzanines, added mech. tees and uprights, noted one work area overspaced beyond 130 ft2, missing forward flow appuratus at the riser, need PRV due to grid system, hydrostatic test postponed until changes are approved.
|
FIR08-00517
| INSP-Final Inspection | 12/31/2008 | 12/31/2008 | 12/31/2008 5:20:35 PM | P | PASS |
|
|
Fire sprinkler permit okay for final.
|
FIR08-00605
| INSP-Sprinkler Rough-in/Hydro | 12/30/2008 | 12/31/2008 | 12/31/2008 5:19:56 PM | P | PART |
|
|
OH installation is not yet approved for cover due to inadequate tenting at several locations, two heads at the SW corner of the pool room are still under spaced, piping under the stairs to the mech. room is not complete. Remainder of rough-in verified against resubmittal plans okayed.
|
BLD08-02129
| FIRE-Final Inspection | 12/31/2008 | 12/31/2008 | 12/31/2008 5:15:17 PM | P | NR |
|
|
Rob Phone#: ###-####
|
FIR08-00733
| INSP-Final Inspection | 12/30/2008 | 12/31/2008 | 12/31/2008 12:15:12 PM | A | PASS |
|
|
New HD's, voltage monitor and elevator shunt trip passed functional testing, fire alarm permit finaled.
|
FIR08-00794
| INSP-Final Inspection | 12/29/2008 | 12/31/2008 | 12/31/2008 12:11:01 PM | A | PASS |
|
|
Scope of fire alarm work tested satisfactory, FA permit finaled.
|
BLD08-02360
| FIRE-Final Inspection | 12/30/2008 | 12/31/2008 | 12/31/2008 12:09:50 PM | A | PASS |
|
|
Noted correction items finished, five exit signs repaired while on site, fire life safety finaled.
|