FIR12-00392
| INSP-Final Inspection | 12/31/2012 | 12/31/2012 | 12/31/2012 3:50:55 PM | P | PASS |
|
|
Permit finaled
|
BLD12-02323
| FIRE-Conference | 12/31/2012 | 12/31/2012 | 12/31/2012 3:47:09 PM | P | DONE |
|
|
Per Romeo Gervais, with the fire alarm functional, it is ok for the owner to begin stocking the store. Public is not allowed until the fire alarm permit has been finaled and the life safety signed off.
|
BLD12-02323
| FIRE-Hydro test above ground | 12/31/2012 | 12/31/2012 | 12/31/2012 2:19:21 PM | P | CANC |
|
|
Wrong inspection type requested.
|
FIR12-00666
| INSP-Final Inspection | 12/31/2012 | 12/31/2012 | 12/31/2012 2:17:37 PM | P | FAIL |
|
|
Plan modifications need to be submitted showing the actual wall layout, new devices/deleted devices and new circuits. Also include the correct model of duct smoke detectors used on the hvac units. I also will need the breaker identified and locked out, building map posted and NFPA 72 forms.
|
FIR12-00693
| INSP-Sprinkler Rough-in | 12/31/2012 | 12/31/2012 | 12/31/2012 1:21:56 PM | P | PART |
|
|
See the city approved plans for residences where the sprinkler rough-in is approved. I noted in two locations where pendant sprinkler heads are missing. Piping can not be covered until a tenting inspection has bee approved.
|
BLD12-02820
| FIRE-Final Inspection | 12/31/2012 | 12/31/2012 | 12/31/2012 12:40:21 PM | P | PASS |
|
|
Life safety passed. ADA approved hardware to be installed on the pocket door before the building inspection.
|
BLD12-01461
| FIRE-Final Inspection | 12/28/2012 | 12/31/2012 | 12/31/2012 9:19:34 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00640
| INSP-Final Inspection | 12/28/2012 | 12/31/2012 | 12/31/2012 9:18:57 AM | A | PASS |
|
|
Permit finaled. Music shuts off upon activation of alarm.
|
FIR12-00663
| INSP-Sprinkler Rough-in/Hydro | 12/27/2012 | 12/31/2012 | 12/31/2012 8:32:27 AM | P | CANC |
|
|
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|