ELE14-03556
| Final | 12/30/2014 | 12/31/2014 | 12/31/2014 2:11:47 PM | P | PASS |
|
|
Completed Kim the owner will be home call with any questions Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
|
ELE14-02468
| Final | 12/30/2014 | 12/31/2014 | 12/31/2014 11:19:35 AM | A | PASS |
|
|
Daryl-please call 20 min prior for access Phone #: ###-#### Final ok
|
ELE13-02994
| Electrical Rough-In | 12/30/2014 | 12/31/2014 | 12/31/2014 10:35:15 AM | A | FAIL |
|
|
Lori-calling in for homeownerplease call meet-Phone #: ###-#### 210.52- Kitchen counter top receptical outlets shall be fed by a minimum of 2 20 amp 120 volt circuits. Small appliance circuits shall be dedicated to counter top recepticals or appliances, no lighting. 2nd circuit required for counter top outlets. 1 circuit for dishwasher/ disposal. 300.4- NM cable shall be secured1 1/4" from framing surface. Where bored holes are less than 1 1/4" from surface nail plate shall be used. 310.15- All 20 amp 120 volt circuits shall be minimum of 12-2 NM cable from start of circuit to end of circuit. Meter base has 30/40 quad on 15 and 20 amp wire.
|
ELE13-03105
| Permanent Service | 12/30/2014 | 12/31/2014 | 12/31/2014 9:12:26 AM | A | PASS |
|
|
The best service Phone #: ###-#### Inspection requested via web by matt miller Performance test complete. p/s u/g n ok
|
ELE13-03105
| Electrical Rough-In | 12/31/2014 | 12/31/2014 | 12/31/2014 9:11:37 AM | P | PASS |
|
|
The best service Phone #: ###-#### Inspection requested via web by matt miller WSR underground rough in ok cover
|