Inspections for the day of: Wednesday, December 31, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03556 Final12/30/201412/31/201412/31/2014 2:11:47 PMPPASS
Completed Kim the owner will be home call with any questions Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
ELE14-02468 Final12/30/201412/31/201412/31/2014 11:19:35 AMAPASS
Daryl-please call 20 min prior for access Phone #: ###-#### Final ok
ELE13-02994 Electrical Rough-In12/30/201412/31/201412/31/2014 10:35:15 AMAFAIL
Lori-calling in for homeownerplease call meet-Phone #: ###-#### 210.52- Kitchen counter top receptical outlets shall be fed by a minimum of 2 20 amp 120 volt circuits. Small appliance circuits shall be dedicated to counter top recepticals or appliances, no lighting. 2nd circuit required for counter top outlets. 1 circuit for dishwasher/ disposal.
300.4- NM cable shall be secured1 1/4" from framing surface. Where bored holes are less than 1 1/4" from surface nail plate shall be used.
310.15- All 20 amp 120 volt circuits shall be minimum of 12-2 NM cable from start of circuit to end of circuit.
Meter base has 30/40 quad on 15 and 20 amp wire.
ELE13-03105 Permanent Service12/30/201412/31/201412/31/2014 9:12:26 AMAPASS
The best service Phone #: ###-#### Inspection requested via web by matt miller Performance test complete. p/s u/g n ok
ELE13-03105 Electrical Rough-In12/31/201412/31/201412/31/2014 9:11:37 AMPPASS
The best service Phone #: ###-#### Inspection requested via web by matt miller WSR underground rough in ok cover