Inspections for the day of: Wednesday, December 31, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03043 Electrical Rough-In12/31/201412/31/201412/31/2014 12:17:32 PMPPASS
Contact is Alan Krishnek Phone #: ###-#### Inspection requested via web by Scott Campbell
Walls ok to cover womens bathroom floor 1 and 2, outlets to fountain in halls floor 1 and 2
ELE12-01075 Final12/31/201412/31/201412/31/2014 11:46:28 AMPPASS
Contact Rob Mairs for access ###-#### Phone #: ###-#### Inspection requested via web by steve ragan
Elevator room Final OK
ELE14-03006 Final12/30/201412/31/201412/31/2014 10:55:42 AMAPASS
Inspection requested via web by Terry Scott
corrections made, final OK
ELE14-02915 Final12/30/201412/31/201412/31/2014 10:49:55 AMPPASS
correction complete, smokes moved to afci. Phone #: ###-#### Inspection requested via web by shane vigil
corrections made, final OK
ELE12-00053 ELE-Aging Inspection12/31/201412/31/201412/31/2014 10:26:51 AM DONE
Called Gary, he will try and get insp. scheduled next week.
ELE14-03261 Final12/30/201412/31/201412/31/2014 10:22:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
final ok
ELE14-03515 Electrical Rough-In12/31/201412/31/201412/31/2014 10:02:59 AMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender
334.30 nm cable shall be secured at intervals no greater than 4 1/2 feet
300.4.1 cable through bored holes shall have protection when hole is less than 1 1/4 inche from edge of framing member
300.4.D cable run parallele to framing member shall be supported so edge of cable is no less than 1 1/4 inch from edge of framing member
210.52 rececptacles shall be installed so that no wall space is greater than 6 foot from a receptacle
210.11 bathroom outlets shall be supplied by 20 amp circuit and supply no other loads.
WUI Zone: soffit cans require 2 hour minimum fire barrier
called contractor
ELE11-00558 Final12/31/201412/31/201412/31/2014 8:50:32 AMAPASS
Access to back yard open, homeowner is out of town Phone #: ###-#### Inspection requested via web by Lynn Cable
final ok
ELE14-03006 Final12/30/201412/31/201412/31/2014 6:04:22 AMACANC
Inspection requested via web by Terry Scott
Contractor doubled the final inspection request, removing one.