Inspections for the day of: Thursday, December 31, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00777 INSP-Sprinkler Rough-in12/30/201512/31/201512/31/2015 11:41:26 AMPPASS
Rough to cover inspection for underground piping passed/complete, approved for cover. Hydrostatic 2 hour @ 200psi test passeed/complete.
BLD15-01826 FIRE-Final Inspection12/30/201512/31/201512/31/2015 11:15:08 AMAPASS
No fire sprinklers, no fire alarms, slide bolt lock removed from tenant side of door at time of inspection, thumb turn deadbolt removed from interior door at time of inspection Life fire safety passed/complete.
BLD15-01708 FIRE-Final Inspection12/30/201512/31/201512/31/2015 11:00:28 AMPFAIL
No fire sprinklers, no fire alarms. Vape shop claimed responsibility for the main entry, north entrance, east side door of main entry has 2 surface mount bolt locks in place, instructed Ryan Phone #: ###-#### that the flush bolts need to be removed and single action door hardware must be installed. Ryan is going to research ways for door to be secure that is code compliant. Tenant needs to install signage on door reading "Door to remain unlocked while space is occupied" Will verify install on next inspection request for life fire safety.
FIR15-00876 INSP-Sprinkler Rough-in12/31/201512/31/201512/31/2015 9:25:27 AMPCANC
Inspection request cancelled, contractor will schedule rough to cover inspection after tenting of the overhead fire sprinkler piping is complete.