Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04582 Electrical Rough-In12/31/201912/31/201912/31/2019 2:02:34 PMPPASS
Above Ceiling inspection. If possible call 30 minuets before so Dan can meet you. Thanks Phone #: ###-#### Inspection requested via web by Brad Hoots
Level 2 corridor grid rough in ok cover
ELE19-04939 Rough-In Permanent Service12/30/201912/31/201912/31/2019 11:19:01 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews
Rough in ok cover p/s o/h n ok
ELE19-04752 Final12/30/201912/31/201912/31/2019 10:30:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ron Zimmerman
210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Breakroom. 300.15- All cables shall terminate in a box. above grid just in from door.
314.25- All boxes shall have covers. Above grid just in from door.
ELE19-03933 Electrical Rough-In12/31/201912/31/201912/31/2019 9:43:27 AMAPASS
Requesting 9:00 am inspection. Install 1 wall sign Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing and disconnecting means confirmed. Rough in ok
ELE19-04379 Final12/30/201912/31/201912/31/2019 9:03:12 AMAPASS
Roy-call for access Phone #: ###-#### Final ok