BLD19-01970
| FIRE-Final Inspection | 12/31/2019 | 12/31/2019 | 1/1/2020 6:48:12 AM | P | PART |
|
|
Partial final inspection for life fire safety complete. Fire sprinkler inspection is complete, fire alarm inspection is partially complete, reference notes under FIR permit for fire alarms items needed to be completed, fire extinguishers are placed with current inspection tags (Inspection tags on fire extinguishers expires in January). 14 day TCO for life fire safety authorized by Ron Johnson with Boise Fire, permit sign off card not provided at time of inspection.
RC Phone #: ###-####
|
FIR19-00957
| INSP-Final Inspection | 12/31/2019 | 12/31/2019 | 1/1/2020 6:46:36 AM | P | PART |
|
|
Partial final inspection for fire alarms complete. A/V device in green room not installed and on order, will be installed when received. 14 day TCO for fire alam permit authorized by Ron Johnson.
Please call Jack at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00925
| INSP-Final Inspection | 12/31/2019 | 12/31/2019 | 12/31/2019 2:26:15 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire alarm inspection is complete.
Charlett Phone #: ###-####
|
FIR19-00742
| INSP-Sprinkler Rough-in/Hydro | 12/30/2019 | 12/31/2019 | 12/31/2019 11:46:19 AM | A | PASS |
|
|
Rough to cover inspection for area of work complete, approved for cover.
Mike Phone #: ###-####
|
BLD19-04541
| FIRE-Final Inspection | 12/30/2019 | 12/31/2019 | 12/31/2019 10:48:21 AM | A | FAIL |
|
|
Service exit sign in back area, sign was not illuminated at time of inspection (south exit door). Provide annual inspection for fire extinguisher. Provide correct signage for main entry reading "Door to remain unlocked while space is occupied."
Zengdi Phone #: ###-####
|
FIR19-00937
| INSP-Sprinkler Rough-in | 12/30/2019 | 12/31/2019 | 12/31/2019 10:22:37 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00779
| INSP-Sprinkler Rough-in | 12/30/2019 | 12/31/2019 | 12/31/2019 9:49:29 AM | A | FAIL |
|
|
Notated areas where piping install does not match city approved drawings. Notated city approved drawings where sidewalls were installed instead of pendant heads, sidewall are a different K factor. 20X20 spacing needs to be verified, no notes on plan allowing 20X20 spacing. 1 1/4 pipe supplying riser is not shown on the drawings.
Overhead rough and tenting, call James before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-02527
| FIRE-Final Inspection | 12/30/2019 | 12/31/2019 | 12/31/2019 8:40:10 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Layton Anderson Inspection cancelled from web by: Layton Anderson
|
BLD19-04934
| FIRE-Final Inspection | 12/30/2019 | 12/31/2019 | 12/31/2019 12:00:00 AM | P | CANC |
|
|
CANCEL by Tobias will call to reschedule//Tobias Phone #: ###-####
|
BLD19-04002
| FIRE-Final Inspection | 12/30/2019 | 12/31/2019 | 12/30/2019 3:27:52 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, hood suppression system inspection is complete, fire extinguishers are placed with current inspection tags, system is not monitored so no knox box. Final life fire safety inspection for scope of work complete.
Taylor Phone #: ###-####
|
FIR19-00529
| INSP-Final Inspection | 12/30/2019 | 12/31/2019 | 12/30/2019 3:15:07 PM | A | PASS |
|
|
Head unit inspection has been completed, this scope of work is finaled.
Phone #: ###-#### Inspection requested via web by Ken Webster
|