Inspections for the day of: Tuesday, December 31, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-01970 FIRE-Final Inspection12/31/201912/31/20191/1/2020 6:48:12 AMPPART
Partial final inspection for life fire safety complete. Fire sprinkler inspection is complete, fire alarm inspection is partially complete, reference notes under FIR permit for fire alarms items needed to be completed, fire extinguishers are placed with current inspection tags (Inspection tags on fire extinguishers expires in January). 14 day TCO for life fire safety authorized by Ron Johnson with Boise Fire, permit sign off card not provided at time of inspection.

RC Phone #: ###-####
FIR19-00957 INSP-Final Inspection12/31/201912/31/20191/1/2020 6:46:36 AMPPART
Partial final inspection for fire alarms complete. A/V device in green room not installed and on order, will be installed when received. 14 day TCO for fire alam permit authorized by Ron Johnson.

Please call Jack at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR19-00925 INSP-Final Inspection12/31/201912/31/201912/31/2019 2:26:15 PMPPASS
Previously noted items have been corrected, final fire alarm inspection is complete.

Charlett Phone #: ###-####
FIR19-00742 INSP-Sprinkler Rough-in/Hydro12/30/201912/31/201912/31/2019 11:46:19 AMAPASS
Rough to cover inspection for area of work complete, approved for cover.

Mike Phone #: ###-####
BLD19-04541 FIRE-Final Inspection12/30/201912/31/201912/31/2019 10:48:21 AMAFAIL
Service exit sign in back area, sign was not illuminated at time of inspection (south exit door). Provide annual inspection for fire extinguisher. Provide correct signage for main entry reading "Door to remain unlocked while space is occupied."

Zengdi Phone #: ###-####
FIR19-00937 INSP-Sprinkler Rough-in12/30/201912/31/201912/31/2019 10:22:37 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00779 INSP-Sprinkler Rough-in12/30/201912/31/201912/31/2019 9:49:29 AMAFAIL
Notated areas where piping install does not match city approved drawings. Notated city approved drawings where sidewalls were installed instead of pendant heads, sidewall are a different K factor. 20X20 spacing needs to be verified, no notes on plan allowing 20X20 spacing. 1 1/4 pipe supplying riser is not shown on the drawings.

Overhead rough and tenting, call James before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-02527 FIRE-Final Inspection12/30/201912/31/201912/31/2019 8:40:10 AMACANC
Phone #: ###-#### >> Inspection requested via web by Layton Anderson Inspection cancelled from web by: Layton Anderson
BLD19-04934 FIRE-Final Inspection12/30/201912/31/201912/31/2019 12:00:00 AMPCANC
CANCEL by Tobias will call to reschedule//Tobias Phone #: ###-####
BLD19-04002 FIRE-Final Inspection12/30/201912/31/201912/30/2019 3:27:52 PMAPASS
No fire sprinklers, no fire alarms, hood suppression system inspection is complete, fire extinguishers are placed with current inspection tags, system is not monitored so no knox box. Final life fire safety inspection for scope of work complete.

Taylor Phone #: ###-####
FIR19-00529 INSP-Final Inspection12/30/201912/31/201912/30/2019 3:15:07 PMAPASS
Head unit inspection has been completed, this scope of work is finaled.

Phone #: ###-#### Inspection requested via web by Ken Webster