Inspections for the day of: Tuesday, December 4, 2001.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00567 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAFAIL
Added by Inspector: 430 On 12/4/2001 11:26:27 AM Add pendants or insulation beneath stage
FIR01-00599 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/4/2001 11:27:13 AM Fire alarm system finaled
BLD01-01181 FIRE-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/4/2001 11:32:33 AM Fire life/safety finaled. Fire door inspected and checked out OK
FIR01-00386 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/4/2001 11:35:33 AM Over head sprinkler system finaled
FIR01-00446 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/4/2001 11:33:37 AM fire alarm system finaled
FIR01-00415 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/4/2001 11:34:39 AM UG fire line finaled
BLD01-02423 FIRE-Final Inspection12/3/200112/4/200112/4/2001 12:00:00 AMANR
All items on the correction notice are not taken care of (fire alarm system) 12/4/2001 5:00:05 PM
FIR01-00498 INSP-Final Inspection12/3/200112/4/200112/4/2001 12:00:00 AMPFAIL
End sprinkler heads along the north and south walls are more than 3-11 1/2 from wall, max. storage height is exceeded through-out store, provide flow switch and check valve on the hose rack system, provide the required spare heads in cabinet, provide draft stops, provide heat and smoke removal vents, hose racks in warehouse are not accessible, hydro test system, provide "fire sprinkler riser" sign on door accessing riser, provide sign on exterior alarm bell, provide "no parking-fire lane" on north exterior wall, remove dumpster to provide clearance for fire dept access, provide verification on duct detectors for store, provide rack information to Boise City for verification of requirements (racks are solid shelves which is not per agreement). Inspection is not complete. I will return by the following day to complete. 12/4/2001 4:48:30 PM
BLD01-02675 FIRE-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMPPASS
Fire sprinkler system finaled today. Correction are made 12/4/2001 4:49:32 PM
FIR01-00567 INSP-Final Inspection12/4/200112/4/200112/4/2001 12:00:00 AMPPASS
Added by Inspector: 430 On 12/4/2001 4:56:18 PM Fire sprinkler system finaled.