Inspections for the day of: Wednesday, December 4, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00407 INSP-Final Inspection12/3/200212/4/200212/4/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/03/2002 at 15:51:58. Contact: ###-####.
BLD02-00955 FIRE-Final Inspection12/3/200212/4/200212/4/2002 12:00:00 AMAPASS
fire life/safety and fire sprinklers finaled 12/4/2002 10:43:23 AM
BLD02-01618 BLD-Other12/4/200212/4/200212/4/2002 12:00:00 AMADONE
Fire alarm work has been performed without a fire alarm permit. I notified sam rogers and the fire alarm contractor.
BLD02-02001 FIRE-Final Inspection12/4/200212/4/200212/4/2002 12:00:00 AMPPART
a temp. occupancy was given with Dave millers permission until the fire alarm drawings have been approved.
FIR02-00470 INSP-Final Inspection12/4/200212/4/200212/4/2002 12:00:00 AMPPART
a temp. occupancy was given with Dave millers permission until the fire alarm drawings have been approved.
FIR02-00381 INSP-Final Inspection12/4/200212/4/200212/4/2002 12:00:00 AMPFAIL
provide test to verify flow for hydraulic calcs., remove switch that shuts off power for the air compressor, provide lockout on aircompressor breaker, provide hydraulic placard 12/4/2002 2:00:28 PM
FIR02-00366 INSP-Final Inspection12/4/200212/4/200212/4/2002 12:00:00 AMPFAIL
the hood in Casa Mexico did not operate and ADT needs to provide a zone map for the fire alarm system at the fire alarm panel 12/5/2002 9:39:36 AM
FIR02-00412 INSP-Final Inspection12/4/200212/4/200212/4/2002 12:00:00 AMPPASS
fire sprinklers finaled 12/4/2002 12:19:06 PM
FIR02-00406 INSP-Sprinkler Rough-in/Hydro12/4/200212/4/200212/4/2002 12:00:00 AMPFAIL
sprinkler piping hydro test is ok. sprinkler piping rough-in is ok. control valve needs to be connected to the existing fire alarm panel and anti-freeze needs to be installed. Drawings will need to be submitted 12/4/2002 3:16:03 PM 12/4/2002 3:17:43 PM