Inspections for the day of: Thursday, December 4, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03822 Electrical Rough-In12/3/200312/4/200312/4/2003 12:00:00 AMAFAIL
Please call for access ###-#### kerry cor. posted met contractor 300.4, 314.16, 334.15(B), 334.23, 250.148 12/4/2003 11:46:50 AM
ELE03-03809 Final12/3/200312/4/200312/4/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 12/3/2003 at 1:22:19 PM. Contact: ###-####. cor. posted met contractor 110.26 250.52(A), 250.53(D)(1)&(2),300.3(B),250.119&200.6, 680.22&22(C), B.C.C. no violations to be retained 12/4/2003 12:50:49 PM
ELE03-03846 Final12/3/200312/4/200312/4/2003 12:00:00 AMAPASS
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 12/4/2003 11:45:34 AM
ELE03-03615 Electrical Rough-In12/3/200312/4/200312/4/2003 12:00:00 AMAPART
Phone #: ###-#### Internet Inspection Request from: Randy Fletcher wall ok 12/4/2003 8:28:46 AM
ELE03-03563 Final12/4/200312/4/200312/4/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/4/2003 at 7:36:46 AM. Contact: ###-####. cor. posted called 110.26 (F)(1)a clearence for panel remove shelf from floor up, 312.3 panel shall be flush with combustible finish, 250.4 (A)(4) grd plug mold at splice box, 250.6(A) plug mold shorted out, and gfci at island counter bad 12/4/2003 1:53:55 PM
ELE03-03852 Rough-In Permanent Service12/4/200312/4/200312/4/2003 12:00:00 AMPPART
Lloyd; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes r/i for walls ok needs show window outlets for final 12/4/2003 3:40:18 PM
ELE03-03758 Electrical Rough-In12/4/200312/4/200312/4/2003 12:00:00 AMPPART
Dan; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes corrections made r/i ok above hard ceiling 12/4/2003 2:41:36 PM