Inspections for the day of: Thursday, December 4, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01031 INSP-Sprinkler Rough-in12/4/200812/4/200812/4/2008 4:37:22 PMPPASS
See the as-built plans for the second floor room that is ok to cover the piping.
FIR08-00500 INSP-Sprinkler Rough-in12/3/200812/4/200812/4/2008 4:36:02 PMPPASS
See the city approved plans for the deficiencies that have been corrected on the first and second floors. I pointed out to Charles that the FDC is possibly located too close to the roof rain gutter and side of the building.
BLD08-01168 FIRE-Final Inspection12/3/200812/4/200812/4/2008 4:32:31 PMPCANC
Not ready for a life safety final
BLD08-00560 FIRE-Final Inspection12/4/200812/4/200812/4/2008 3:42:27 PMPPASS
fire life safety passed
BLD08-02480 FIRE-Final Inspection12/4/200812/4/200812/4/2008 2:39:07 PMPPASS
Life safety passed.
BLD08-02282 FIRE-Final Inspection12/3/200812/4/200812/4/2008 11:41:49 AMAFAIL
Provide sprinkler protection for the two offices and the coolers, remove the thumbturn deadbolt from the west exit, remove the deadbolt and provide lever hardware on the southeast exit door and tag and mount the fire extinguishers.
BLD08-00890 FIRE-Final Inspection12/2/200812/4/200812/4/2008 11:23:03 AMAPASS
Life safety passed
FIR08-00602 INSP-Final Inspection12/3/200812/4/200812/4/2008 11:22:34 AMAFAIL
Provide test reports, get decision from sam rogers on the "future expansion" on the second floor (no notification is functional), and provide modifications as required due to the strobes being blocked on the first floor due to shelving.