Inspections for the day of: Thursday, December 4, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy James
TitleMEC-COM/RES INSPECTOR
Phone #794-9461
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC08-03481 Final12/3/200812/4/200812/4/2008 4:09:10 PMPFAIL
Please inspect late afternoon. Thanks, April.
Phone #: ###-#### Internet Inspection Request from: April Sims
no adult home could not enter home
MEC08-01936 Final12/4/200812/4/200812/4/2008 3:53:41 PMPPASS
JOB CONTACT IS ANDY MAPP Phone #: ###-#### Internet Inspection Request from: ADAM WARR
MEC08-03484 Final12/3/200812/4/200812/4/2008 3:25:43 PMPPASS
Please inspect late afternoon. Call with any problems. Thanks, April. Phone #: ###-#### Internet Inspection Request from: April Sims
MEC08-03419 Final12/3/200812/4/200812/4/2008 3:16:14 PMPPASS
Contact is Jean Benton - would like any time after 2:00pm Phone #: ###-#### Internet Inspection Request from: Wayne Van Cleave
MEC08-03490 Final12/4/200812/4/200812/4/2008 2:44:59 PMPPASS
see tenant meghan ###-####. thanks Phone #: ###-#### Internet Inspection Request from: Kelea Dunne
MEC08-03367 Pressure Test12/4/200812/4/200812/4/2008 1:58:08 PMPPASS
steve - please call 1/2 hr prior so he can meet you there Phone #: ###-####
20#
MEC08-03367 Final12/4/200812/4/200812/4/2008 1:57:51 PMPPASS
steve - please call 1/2 hr prior so he can meet you there Phone #: ###-####
MEC08-03463 Pressure Test12/4/200812/4/200812/4/2008 11:18:27 AMPPASS
darren - suite 104 Phone #: ###-####
60#
MEC08-03482 Rough-in12/3/200812/4/200812/4/2008 10:56:38 AMPPASS
A+ Engery Phone #: ###-####
MEC08-03482 Final12/4/200812/4/200812/4/2008 10:56:24 AMPPASS
A+ Engery Phone #: ###-####
MEC08-02377 Final12/4/200812/4/200812/4/2008 10:34:04 AMAFAIL
gas regulators are required to be mounted upright and vented 3' above air intake to rtu's air intake when within 10', complete condensate trap to rtu's
MEC08-01386 Final12/3/200812/4/200812/4/2008 10:23:01 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Doramus Cassi
type 1 hood undersized for appliance under, need 18" clearance to top of hood from combustibles, need air balance report, hinge on grease duct exhaust and grease collector
MEC08-03475 Final12/3/200812/4/200812/4/2008 10:20:40 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lori Michel