Inspections for the day of: Friday, December 4, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00350 General Inspection12/4/200912/4/200912/4/2009 4:10:37 PMPPASS
looked ok
ELE09-01285 Electrical Rough-In12/3/200912/4/200912/4/2009 4:10:05 PMPPASS
ceiling cover, Toby Groves, ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis outside soffits only ok to cover, no esc this project
ELE09-02312 Permanent Service12/3/200912/4/200912/4/2009 3:54:52 PMPFAIL
Guy Phone #: ###-#### met contractor early, looked at part of installation, talked with 412, told contractor only 1 service allowed for building per NEC 230, no esc this project
ESC08-00776 General Inspection12/4/200912/4/200912/4/2009 3:22:06 PMPPASS
looked ok
ELE09-02338 Final12/4/200912/4/200912/4/2009 2:38:15 PMPPASS
Rick at ###-#### or Kelly at ###-####
Starbucks Inside Albertsons Store . Electrical Phone #: ###-#### Internet Inspection Request from: Kelly Felin ok to final, signed structural card, no esc this project
ELE09-02319 Electrical Rough-In12/3/200912/4/200912/4/2009 2:09:41 PMPPASS
WE ARE EXPECTING TO BE DONE AT ABOUT 1:30, WE WOULD LIKE TO BE THERE WHEN YOU INSPECT IF IT WORKS OUT. WE WILL BE CLEANING UP FOR A WHILE SO HOPEFULLY WE WILL SEE YOU THERE. THANKS. Phone #: ###-#### Internet Inspection Request from: Jamie Winters ric ok, told electrician to change room count to 11 rooms on permit
ELE09-02319 Permanent Service12/4/200912/4/200912/4/2009 2:09:24 PMPPASS
WE ARE EXPECTING TO BE DONE AT ABOUT 1:30, WE WOULD LIKE TO BE THERE WHEN YOU INSPECT IF IT WORKS OUT. WE WILL BE CLEANING UP FOR A WHILE SO HOPEFULLY WE WILL SEE YOU THERE. THANKS. Phone #: ###-#### Internet Inspection Request from: Jamie Winters p/s u/g n ok
ELE09-01932 Electrical Rough-In12/3/200912/4/200912/4/2009 1:08:39 PMPFAIL
Late in the afternoon if possible. Nick is the contact his no. is ###-####. Phone #: ###-#### Internet Inspection Request from: Shawna Gates called, left correction notice,NEC 110.12(A) shall close unused openings, 300.11(a)(1) cables and raceways shall not be supported bt ceiling grid wires, 314.25 shall provide cobers for switches and receptacles, 406.4 receptacles shall be securely supported, 330.30(A) mc cable shall be secured within 12" of box, BCC No violations shall be retained
ELE09-02282 Final12/4/200912/4/200912/4/2009 12:01:56 PMPPASS
Steve Phone #: ###-#### ok to final, signed structural card, no esc this project
ELE07-03990 Final12/4/200912/4/200912/4/2009 9:53:28 AMAPASS
ok to final, no esc this project
ELE09-02347 Electrical Rough-In12/3/200912/4/200912/4/2009 9:51:53 AMACANC
Please call 1/2 hour before inspection so we can meet you there. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty
ELE06-00293 ELE-Aging Inspection12/4/200912/4/200912/4/2009 9:30:50 AM DONE
no activity
ELE07-03996 ELE-Aging Inspection12/4/200912/4/200912/4/2009 9:30:27 AM DONE
no activity
ELE09-01418 Electrical Rough-In12/3/200912/4/200912/4/2009 9:24:28 AMAPASS
Inspection for the groud work
call Dustin at listed number with Questions
Thank you Phone #: ###-#### Internet Inspection Request from: David Oliver ok to cover u/g from transformer to cell building- part will be core drilled across parking lot, no esc this project
ELE09-02346 Permanent Service12/3/200912/4/200912/4/2009 9:02:48 AMAPASS
service located in south west back corner of lot. Phone #: ###-#### Internet Inspection Request from: Cindie Swaim p/s o/h n ok, no esc this project
ELE09-02310 Electrical Rough-In12/3/200912/4/200912/4/2009 8:16:11 AMAPASS
Underground Phone #: ###-#### Internet Inspection Request from: Mark Sessions ok to cover u/g to panels (4) anop, no esc this project