Inspections for the day of: Tuesday, December 4, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00604 INSP-Sprinkler Rough-in/Hydro12/4/201212/4/201212/4/2012 4:27:53 PMPNR
Guages below 200 psi. @ approx 190.
FIR12-00625 INSP-Sprinkler Rough-in12/4/201212/4/201212/4/2012 4:24:56 PMPPART
Okay to cover kitchen area drop ceiling with the exception of adjustments to cover a pocket above the mop sink. Basement area including the new cooler is also approved.
BLD12-01740 FIRE-Final Inspection12/4/201212/4/201212/4/2012 4:21:14 PMPNR
Pending project finishes
BLD12-01716 FIRE-Final Inspection12/4/201212/4/201212/4/2012 4:17:51 PMAPASS
Fire life safety inspection completed satisfactory.
BLD12-01740 FIRE-Final Inspection12/4/201212/4/201212/4/2012 1:40:32 PMADONE
On site conference with contractor regarding conditions for fire life safety final approval.
BLD12-02261 FIRE-Final Inspection12/4/201212/4/201212/4/2012 1:39:28 PMAPASS
Fire life safety inspection completed acceptable.
FIR12-00673 INSP-Final Inspection12/4/201212/4/201212/4/2012 1:38:12 PMPPART
Site inspection and functional testing completed in conjunction with a related permit. However, approved plans were missing on site- need to provide plans and permit card for verification and signature- final pending.
FIR12-00633 INSP-Final Inspection12/4/201212/4/201212/4/2012 1:34:56 PMPPASS
Fire alarm permit finaled. Inspection passed.
FIR12-00633 INSP-Sprinkler Rough-in/Hydro12/4/201212/4/201212/4/2012 1:28:26 PMAPART
Functional testing completed for the relocated devices.