ELE13-03187
| Electrical Rough-In | 12/4/2013 | 12/4/2013 | 12/4/2013 2:51:46 PM | P | PASS |
|
|
Walls and ceilings. Patrick is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut walls only, no ceiling ready, ok cover
|
ELE13-03332
| Electrical Rough-In | 12/4/2013 | 12/4/2013 | 12/4/2013 2:24:14 PM | P | FAIL |
|
|
underground inspection needed call steve with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig called left correction notice, see posted for bends, no rock cover, spacing, no cover before inspection
|
ELE13-03360
| Electrical Rough-In | 12/3/2013 | 12/4/2013 | 12/4/2013 1:20:22 PM | P | PASS |
|
|
floor heat Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, ok cover floor heat
|
ELE13-03155
| Electrical Rough-In | 12/4/2013 | 12/4/2013 | 12/4/2013 12:11:31 PM | P | PASS |
|
|
UG pipe insp// Clyde Phone #: ###-#### ok cover u/g house to garage only
|
GCE13-00201
| GCE-Temporary Service | 12/3/2013 | 12/4/2013 | 12/4/2013 10:12:31 AM | A | FAIL |
|
|
Brad ###-#### called, shall provide job id sticker, address, IPCO requires 6"x6" pole for o/h service, NEC 250.53(G) shall drive in ground rod, left correction notice
|
ELE13-02977
| Electrical Rough-In | 12/3/2013 | 12/4/2013 | 12/4/2013 9:04:16 AM | A | PASS |
|
|
Lock box code is 2343. Please inspect infloor heating Phone #: ###-#### >> Inspection requested via web by Brad Girard called contractor to add heat to permit, ok cover floor heat only
|
ELE13-03327
| Electrical Rough-In | 12/3/2013 | 12/4/2013 | 12/4/2013 8:25:23 AM | A | PASS |
|
|
carl Phone #: ###-#### concrete encased electrode ok pour
|