ELE14-03188
| Final | 12/4/2014 | 12/4/2014 | 12/4/2014 3:07:52 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender ok final
|
ELE14-03317
| Temporary Service | 12/4/2014 | 12/4/2014 | 12/4/2014 2:58:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, t/s u/g n ok
|
ELE14-02458
| Permanent Service | 12/4/2014 | 12/4/2014 | 12/4/2014 2:23:20 PM | P | FAIL |
|
|
Garage code for the back 1668 if no one is there. Call Troy at ###-#### with any questions Phone #: ###-#### Inspection requested via web by Don Conley called, left message, NEC 110.24 shall post available fault code at service, shall remove existing service for 6 service drops
|
ELE14-03322
| Electrical Rough-In | 12/4/2014 | 12/4/2014 | 12/4/2014 1:20:01 PM | P | PASS |
|
|
Call for access Phone #: 6299948 >> Inspection requested via mobile web by David McClellan ri ok g,h,i office areas only
|
ELE14-03162
| Final | 12/3/2014 | 12/4/2014 | 12/4/2014 9:59:34 AM | A | PASS |
|
|
Please call Dave Mackey prior to inspection, ###-#### Phone #: ###-#### Inspection requested via web by David Mackey called, ok final
|
ELE14-03332
| Permanent Service | 12/3/2014 | 12/4/2014 | 12/4/2014 9:44:19 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL met contractor, NEC 110.24(A) service equipment shall be marked with maximum available fault current and date of calculation and be durable for conditions
|
ELE14-03323
| Rough-In Permanent Service | 12/3/2014 | 12/4/2014 | 12/4/2014 9:08:59 AM | A | PASS |
|
|
Inspection requested via web by Rowdy Monroe ri ok, p/s u/g n ok
|
ELE14-03071
| Electrical Rough-In | 12/3/2014 | 12/4/2014 | 12/4/2014 7:14:10 AM | A | CANC |
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
|