Inspections for the day of: Thursday, December 4, 2014.
Number of inspections: 6
Percentage of inspections complete: 83 %
Percentage of inspections not complete: 17 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01666 FIRE-Final Inspection12/2/201412/3/2014 A 
Chad Phone #: ###-####
FIR14-00460 INSP-Sprinkler Rough-in12/4/201412/4/201412/9/2014 3:15:39 PMPFAIL
Inspection at basement level completed - missing coverage at the storage room below north stairway per plan, obstructed coverage at the south stairway, installation does not match approved plan, mixed temps and types of heads at the woodshop area. Need to provide a plan modification for resubmittal prior to final.
BLD14-03136 FIRE-Final Inspection12/3/201412/4/201412/4/2014 2:45:13 PMPPASS
Fire life safety inspection approved pending removal of keyed lock deadbolts at office doors.
BLD14-02950 FIRE-Final Inspection12/4/201412/4/201412/4/2014 2:44:02 PMPPASS
C/N items finished. Fire life safety final approved.
FIR14-00775 INSP-Final Inspection12/4/201412/4/201412/4/2014 2:42:59 PMPPASS
Fire sprinkler work passed final walkthrough. Permit finaled.
FIR14-00472 INSP-Final Inspection12/3/201412/4/201412/4/2014 2:41:42 PMAPASS
Fire alarm work passed inspection. Permit finaled.