Inspections for the day of: Thursday, December 5, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02691 Final12/4/200212/5/200212/5/2002 12:00:00 AMANR
zane ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie will post correction for unlisted x-ray equipment 12/5/2002 12:30:30 PM
ELE02-03729 Temporary Service12/4/200212/5/200212/5/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/04/2002 at 16:10:26. Contact: ###-####.
t/s o/h new ok 12/5/2002 10:52:43 AM
ELE02-03697 Electrical Rough-In12/4/200212/5/200212/5/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 12/04/2002 at 16:11:11. Contact: ###-####. u/g for ID power and phone we do not inspect that , and was not done by electrical contractor 12/5/2002 10:55:11 AM
ELE02-03616 Final12/4/200212/5/200212/5/2002 12:00:00 AMAPASS
Contact:Chris Carmine - he will meet you there; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok, met with Chris, needs to tie power pole and wiremold together 300.10,12 12/5/2002 1:12:36 PM
ELE02-02728 Electrical Rough-In12/4/200212/5/200212/5/2002 12:00:00 AMPPART
call 1st ###-#### new addition to house ok garage addition not ready yet 12/5/2002 5:47:03 PM
ELE02-02660 Final12/4/200212/5/200212/5/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/04/2002 at 19:32:02. Contact: ###-####. ok 12/5/2002 6:17:48 PM
ELE02-03286 Electrical Rough-In12/5/200212/5/200212/5/2002 12:00:00 AMPPART
mid-afternoon ###-#### u/g ok 12/5/2002 4:34:07 PM
ELE02-02691 Final12/5/200212/5/200212/5/2002 12:00:00 AMPPART
zane; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie temp occupancy only cor. posted called 110.2,and 1997 UAC section 107 xray equip. shall be listed, 400.8(2), 517.78(C), 314.29, 210.8(B)(1), note xray equip shall not be used before it is listed, by testing lab 12/5/2002 4:11:44 PM
ELE02-03481 Permanent Service12/5/200212/5/200212/5/2002 12:00:00 AMPPASS
for homework terrace; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s o/h new ok 12/5/2002 5:06:44 PM
ELE02-03750 Electrical Rough-In12/4/200212/5/200212/4/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 12/04/2002 at 14:10:25. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 12/04/2002 at 15:40:08.