Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-01894 FIRE-Final Inspection12/4/200212/5/200212/5/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 12/04/2002 at 09:41:20. Contact: ###-####. need clarification on location of hydrants in relation to the cab road; per Dave Miller he will talk with Ken Schneider about this 12/5/2002 5:02:36 PM
FIR02-00441 INSP-Final Inspection12/4/200212/5/200212/5/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 12/04/2002 at 11:52:38. Contact: ###-####. install per plans or provide resubmittals for review 12/5/2002 9:33:25 AM
BLD02-01951 FIRE-Final Inspection12/5/200212/5/200212/5/2002 12:00:00 AMAFAIL
need to test duct detectors and have smoke detector above panel reinstalled - the panel and duct detectors are all exsisting; need pull station repaired (open and the panel not in alarm); need resubmittals for sprinkler plans - not installed per plans
FIR02-00425 INSP-Conference12/4/200212/5/200212/5/2002 12:00:00 AMPPART
chris- ###-#### panel will be located in the riser room as indicated on the plans 12/5/2002 5:03:03 PM