ELE05-04248
| Temporary Service | 12/5/2005 | 12/5/2005 | 12/5/2005 4:41:39 PM | P | FAIL |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, grounded conductor shall connect to equipment grounding conductor
|
ELE05-03772
| Electrical Rough-In | 12/5/2005 | 12/5/2005 | 12/5/2005 4:40:18 PM | P | FAIL |
|
|
caren; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met with owner, left corr notice,334.30 nm cable shall be stapled within 12" of panel and range,312.5 conductors entering enclosures shall be protected from abrasion,gec and outside boxes, 314.17(C) nm cable jacket shall extend minimum 1/4" inside box,by stairs
|
ELE05-02944
| Final | 12/5/2005 | 12/5/2005 | 12/5/2005 4:36:51 PM | P | FAIL |
|
|
Final Inspection ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin called contr, left corr notice, 110.2 equipment shall be acceptable only if approved(ozone generator)
|
ELE05-03782
| Final | 12/5/2005 | 12/5/2005 | 12/5/2005 3:24:28 PM | P | PASS |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
|
ELE05-04357
| Rough-In Permanent Service | 12/5/2005 | 12/5/2005 | 12/5/2005 3:23:00 PM | P | PASS |
|
|
brian ###-#### ric ok, p/s u/g n ok
|
ELE05-04286
| Temporary Service | 12/5/2005 | 12/5/2005 | 12/5/2005 1:26:38 PM | P | PASS |
|
|
jean; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, t/s u/g n ok
|
ELE05-04250
| Temporary Service | 12/5/2005 | 12/5/2005 | 12/5/2005 12:14:20 PM | P | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, t/s u/g n ok
|
ELE05-04339
| Electrical Rough-In | 12/2/2005 | 12/5/2005 | 12/5/2005 10:10:22 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 12/2/2005 at 3:27:29 PM. Contact: ###-####. see rip
|
ELE05-04319
| Electrical Rough-In | 12/2/2005 | 12/5/2005 | 12/5/2005 9:29:46 AM | A | PASS |
|
|
underground inspection; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen u/g ok to cover
|
ELE05-04345
| Electrical Rough-In | 12/2/2005 | 12/5/2005 | 12/5/2005 8:59:59 AM | A | CANC |
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see final
|
ELE05-03527
| Final | 12/2/2005 | 12/5/2005 | 12/5/2005 8:37:01 AM | A | PASS |
|
|
ray; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left survey,406.4)A) recpt shall be rigidly mounted, ok to final
|
ELE05-04339
| Rough-In Permanent Service | 12/5/2005 | 12/5/2005 | 12/5/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/2/2005 at 3:27:29 PM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE05-04345
| Final | 12/5/2005 | 12/5/2005 | 12/5/2005 12:00:00 AM | P | PASS |
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie met owner, told to add gnd screw in metal box, ok to final
|