Inspections for the day of: Monday, December 5, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04248 Temporary Service12/5/200512/5/200512/5/2005 4:41:39 PMPFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, grounded conductor shall connect to equipment grounding conductor
ELE05-03772 Electrical Rough-In12/5/200512/5/200512/5/2005 4:40:18 PMPFAIL
caren; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met with owner, left corr notice,334.30 nm cable shall be stapled within 12" of panel and range,312.5 conductors entering enclosures shall be protected from abrasion,gec and outside boxes, 314.17(C) nm cable jacket shall extend minimum 1/4" inside box,by stairs
ELE05-02944 Final12/5/200512/5/200512/5/2005 4:36:51 PMPFAIL
Final Inspection ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin called contr, left corr notice, 110.2 equipment shall be acceptable only if approved(ozone generator)
ELE05-03782 Final12/5/200512/5/200512/5/2005 3:24:28 PMPPASS
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
ELE05-04357 Rough-In Permanent Service12/5/200512/5/200512/5/2005 3:23:00 PMPPASS
brian ###-#### ric ok, p/s u/g n ok
ELE05-04286 Temporary Service12/5/200512/5/200512/5/2005 1:26:38 PMPPASS
jean; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, t/s u/g n ok
ELE05-04250 Temporary Service12/5/200512/5/200512/5/2005 12:14:20 PMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, t/s u/g n ok
ELE05-04339 Electrical Rough-In12/2/200512/5/200512/5/2005 10:10:22 AMACANC
Scheduled by a contractor via Hello! on 12/2/2005 at 3:27:29 PM. Contact: ###-####. see rip
ELE05-04319 Electrical Rough-In12/2/200512/5/200512/5/2005 9:29:46 AMAPASS
underground inspection; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen u/g ok to cover
ELE05-04345 Electrical Rough-In12/2/200512/5/200512/5/2005 8:59:59 AMACANC
robert ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see final
ELE05-03527 Final12/2/200512/5/200512/5/2005 8:37:01 AMAPASS
ray; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left survey,406.4)A) recpt shall be rigidly mounted, ok to final
ELE05-04339 Rough-In Permanent Service12/5/200512/5/200512/5/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/2/2005 at 3:27:29 PM. Contact: ###-####. ric ok, p/s u/g n ok
ELE05-04345 Final12/5/200512/5/200512/5/2005 12:00:00 AMPPASS
robert ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie met owner, told to add gnd screw in metal box, ok to final