FIR05-00635
| INSP-Alarm Testing | 12/5/2005 | 12/5/2005 | 12/5/2005 4:17:12 PM | P | PASS |
|
|
c/n items have been performed, fire alarm passed inspection.
|
FIR05-00730
| INSP-Final Inspection | 12/5/2005 | 12/5/2005 | 12/5/2005 3:23:42 PM | P | FAIL |
|
|
The smoke detector above the FACP failed to function properly.
|
FIR05-00647
| INSP-Final Inspection | 12/5/2005 | 12/5/2005 | 12/5/2005 2:24:05 PM | P | PASS |
|
|
Fire sprinkler passed inspection, permit finaled.
|
BLD05-02133
| FIRE-Final Inspection | 12/2/2005 | 12/5/2005 | 12/5/2005 12:42:32 PM | A | FAIL |
|
|
Post the required "no smoking" signs, provide and install one 2A10BC fire extinguisher with a current inspection tag along a normal path of travel with the handle no higher than 48" AFF, repair exit sign at main entry/exit, maintain clearance between shelving and cooler door.
|
MIS05-00097
| FIR-Final | 12/2/2005 | 12/5/2005 | 12/5/2005 11:53:41 AM | A | PASS |
|
|
c/n items are complete, fire life safety is acceptable.
|
FIR05-00570
| INSP-Sprinkler Rough-in | 12/2/2005 | 12/5/2005 | 12/5/2005 11:34:47 AM | A | PART |
|
|
Verified the unsprinklered cavity at the west dormer has been completely filled with noncombustible insulation per the exception of NFPA 13 8.14.1.2.7. Overhead rough-in is good for cover.
|
FIR05-00730
| INSP-Final Inspection | 12/2/2005 | 12/5/2005 | 12/5/2005 11:24:05 AM | A | FAIL |
|
|
Unable to test smoke detector above panel due to insufficient test smoke provided, duct detector as shown on approved plans is not installed (contractor verifies it is under 2000 cfm), inspection rescheduled for this afternoon.
|
BLD05-00672
| FIRE-Final Inspection | 12/2/2005 | 12/5/2005 | 12/5/2005 10:13:45 AM | A | PASS |
|
|
c/n items have been completed, fire life safety passed inspection.
|
FIR05-00528
| INSP-Final Inspection | 12/5/2005 | 12/5/2005 | 12/5/2005 10:11:21 AM | A | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00265
| INSP-Final Inspection | 12/5/2005 | 12/5/2005 | 12/5/2005 10:10:40 AM | A | PASS |
|
|
UG fire supply finaled.
|
FIR05-00528
| INSP-Sprinkler Rough-in/Hydro | 12/2/2005 | 12/5/2005 | 12/5/2005 10:04:57 AM | A | PASS |
|
|
Resubmittals have been reviewed and verified, c/n items are complete, fire sprinkler permit finaled.
|