Inspections for the day of: Tuesday, December 5, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03000 FIRE-Final Inspection12/4/200612/5/200612/5/2006 3:06:14 PMACANC
Final pending project related alarm permit inspection scheduled for 12/6.
FIR06-00951 INSP-Final Inspection12/5/200612/5/200612/5/2006 3:03:25 PMPDEFR
Rescheduled for 12/6 am per phone call with contractor.
FIR06-00725 INSP-Sprinkler Rough-in12/4/200612/5/200612/5/2006 2:49:53 PMPPART
Sprinkler rough-in is okay for cover at the drop ceilings.
FIR06-00496 INSP-Sprinkler Rough-in/Hydro12/4/200612/5/200612/5/2006 2:44:16 PMAPART
AG hydrostatic test completed satisfactory.
FIR06-00927 INSP-Sprinkler Rough-in/Hydro12/4/200612/5/200612/5/2006 2:43:26 PMAFAIL
Heads are overspaced to an adjacent wall as installed at pod #3. Sprinkler rough-in is acceptable for cover at the drop ceilings in pod #6.
BLD06-00981 FIRE-Final Inspection12/1/200612/5/200612/5/2006 12:08:04 PMAFAIL
Door hardware as installed at the second exit to the roof from the common corridor is not approved.
BLD06-02129 FIRE-Final Inspection12/4/200612/5/200612/5/2006 12:06:43 PMAFAIL
Need to repair the exit signs and emergency lighting in the warehouse area, provide address numbers per fire code review notes, remove the manual thumbturn at the main entry/exit door, provide a current annual fire sprinkler system inspection to be completed by a licensed contractor.