BLD06-01821
| FIRE-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 3:48:36 PM | P | FAIL |
|
|
Provide indicator and sticker at the main exit. Provide fire extinguishers as discussed. Provide exit sign/emergency light at the warehouse door as discussed. The fire dept. access needs worked out with the new buildings access.
|
BLD07-00948
| FIRE-Final Inspection | 12/4/2007 | 12/5/2007 | 12/5/2007 3:06:42 PM | A | FAIL |
|
|
The duct smoke detectors have been installed on the supply side not the return side as required per the IMC. The testing has been stopped.
|
BLD07-01451
| FIRE-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 2:46:27 PM | P | PASS |
|
|
Life safety passed.
|
BLD07-02705
| FIRE-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 2:26:29 PM | P | FAIL |
|
|
Provide an exit sign outside of the office door that leads to the exterior exit as marked on the city approved plans. Provide non locking hardware on this same door as marked on the plans.
|
BLD07-02675
| FIRE-Final Inspection | 12/5/2007 | 12/5/2007 | 12/5/2007 2:25:17 PM | P | FAIL |
|
|
The existing sprinkler heads along the new demising wall are overspaced and a head is missing from the entry into the conference room. This work will require permits.
|
FIR07-00449
| INSP-Sprinkler Rough-in | 12/4/2007 | 12/5/2007 | 12/5/2007 1:22:32 PM | A | PASS |
|
|
See the city approved plans for the two location in the entry vestibules where the sprinkler hangers are ok to cover.
|
FIR07-00640
| INSP-Alarm Testing | 12/4/2007 | 12/5/2007 | 12/5/2007 11:30:36 AM | A | FAIL |
|
|
All of the a/v's were tested. See the city approved plans for one that did not work and will need replaced and retested. When we started testing the smoke detectors I found that the operation of the smoke detectors in the middle of the corridors did not match the alarm matrix which showed their operation releasing the doors. As programed now only the smoke detectors near the doors are releasing the door hold opens. This would be ok but not all of the smoke detectors are with in 5'-0" of the doors as required. The inspection was stopped until a decision is made on how the smoke detectors are going to function.
|
FIR07-00581
| INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 11:27:22 AM | A | FAIL |
|
|
Overhead hydro test failed
|
FIR07-00580
| INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 11:26:49 AM | A | FAIL |
|
|
Overhead hydro test failed
|
FIR07-00585
| INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 11:26:26 AM | A | FAIL |
|
|
Overhead hydro test failed
|
FIR07-00582
| INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 11:25:19 AM | A | PASS |
|
|
OH Hydro Inspection passed
|
FIR07-00586
| INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 11:24:47 AM | A | PASS |
|
|
OH Hydro Inspection passed
|
FIR07-00941
| INSP-Sprinkler Rough-in | 12/4/2007 | 12/5/2007 | 12/5/2007 10:37:10 AM | A | FAIL |
|
|
Two arm overs more than 24 inches, see plans for details.KR
|