Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01821 FIRE-Final Inspection12/5/200712/5/200712/5/2007 3:48:36 PMPFAIL
Provide indicator and sticker at the main exit. Provide fire extinguishers as discussed. Provide exit sign/emergency light at the warehouse door as discussed. The fire dept. access needs worked out with the new buildings access.
BLD07-00948 FIRE-Final Inspection12/4/200712/5/200712/5/2007 3:06:42 PMAFAIL
The duct smoke detectors have been installed on the supply side not the return side as required per the IMC. The testing has been stopped.
BLD07-01451 FIRE-Final Inspection12/5/200712/5/200712/5/2007 2:46:27 PMPPASS
Life safety passed.
BLD07-02705 FIRE-Final Inspection12/5/200712/5/200712/5/2007 2:26:29 PMPFAIL
Provide an exit sign outside of the office door that leads to the exterior exit as marked on the city approved plans. Provide non locking hardware on this same door as marked on the plans.
BLD07-02675 FIRE-Final Inspection12/5/200712/5/200712/5/2007 2:25:17 PMPFAIL
The existing sprinkler heads along the new demising wall are overspaced and a head is missing from the entry into the conference room. This work will require permits.
FIR07-00449 INSP-Sprinkler Rough-in12/4/200712/5/200712/5/2007 1:22:32 PMAPASS
See the city approved plans for the two location in the entry vestibules where the sprinkler hangers are ok to cover.
FIR07-00640 INSP-Alarm Testing12/4/200712/5/200712/5/2007 11:30:36 AMAFAIL
All of the a/v's were tested. See the city approved plans for one that did not work and will need replaced and retested. When we started testing the smoke detectors I found that the operation of the smoke detectors in the middle of the corridors did not match the alarm matrix which showed their operation releasing the doors. As programed now only the smoke detectors near the doors are releasing the door hold opens. This would be ok but not all of the smoke detectors are with in 5'-0" of the doors as required. The inspection was stopped until a decision is made on how the smoke detectors are going to function.
FIR07-00581 INSP-Sprinkler Rough-in/Hydro12/4/200712/5/200712/5/2007 11:27:22 AMAFAIL
Overhead hydro test failed
FIR07-00580 INSP-Sprinkler Rough-in/Hydro12/4/200712/5/200712/5/2007 11:26:49 AMAFAIL
Overhead hydro test failed
FIR07-00585 INSP-Sprinkler Rough-in/Hydro12/4/200712/5/200712/5/2007 11:26:26 AMAFAIL
Overhead hydro test failed
FIR07-00582 INSP-Sprinkler Rough-in/Hydro12/4/200712/5/200712/5/2007 11:25:19 AMAPASS
OH Hydro Inspection passed
FIR07-00586 INSP-Sprinkler Rough-in/Hydro12/4/200712/5/200712/5/2007 11:24:47 AMAPASS
OH Hydro Inspection passed
FIR07-00941 INSP-Sprinkler Rough-in12/4/200712/5/200712/5/2007 10:37:10 AMAFAIL
Two arm overs more than 24 inches, see plans for details.KR