ELE08-02889
| Final | 12/5/2008 | 12/5/2008 | 12/5/2008 3:48:30 PM | P | PASS |
|
|
Contact Ron for access. Phone #: ###-#### Internet Inspection Request from: Bill Hines ok to final, signed occupancy card, no esc this project
|
ESC08-00070
| General Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 2:50:22 PM | P | PASS |
|
|
no work being done, looked ok
|
ESC08-00906
| General Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 2:49:00 PM | A | PASS |
|
|
looked ok
|
ELE08-02898
| Final | 12/5/2008 | 12/5/2008 | 12/5/2008 2:17:24 PM | P | PASS |
|
|
Contact Ron for access Phone #: ###-#### Internet Inspection Request from: Bill Hines ok to final signed occupancy card, no esc this project
|
ELE08-03066
| Final | 12/5/2008 | 12/5/2008 | 12/5/2008 1:16:57 PM | P | PASS |
|
|
charlene Phone #: ###-#### ok to final, signed structural card, no esc this project
|
ELE08-03066
| Electrical Rough-In | 12/5/2008 | 12/5/2008 | 12/5/2008 12:32:34 PM | P | PASS |
|
|
charlene Phone #: ###-#### ric ok, no esc this project
|
ELE08-03153
| Permanent Service | 12/4/2008 | 12/5/2008 | 12/5/2008 9:40:30 AM | A | FAIL |
|
|
kent Note: 36th garden cntr - in front two condos - if need more information please calll Phone #: ###-#### called left correction notice,NEC312.5 all conductors entering enclosure shall have abrasion protection, 110.12(A) unused openings shall be closed, 250.92(A),(B) service raceways shall be bonded,BCC all u/g shall be inspected before cover, note: corrections shall be made within 2 working days
|
ELE08-03166
| Final | 12/4/2008 | 12/5/2008 | 12/5/2008 8:49:45 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ok to final, signed occupancy card, no esc this project
|
ELE08-00279
| ELE-Aging Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 8:37:00 AM | | DONE |
|
|
talked to contractor, see final, no esc this project
|
ELE08-00279
| Final | 12/5/2008 | 12/5/2008 | 12/5/2008 8:36:40 AM | A | PASS |
|
|
ok to final, no esc this project
|