FIR08-00637
| INSP-Final Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 3:52:14 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 12/5/2008 at 9:27:52 AM. Contact: ###-####.
|
FIR08-00740
| INSP-Final Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 3:33:52 PM | P | FAIL |
|
|
The alarm system as installed has been tested. The strobes in classroom #4 were changed to 75cd to meet NFPA 72 spacing requirements and end of line voltages verified. I have deferred the requirements of off site monitoring and the annunciation of a trouble signal at the remote annunciatior to the fire alarm plan reviewer and sam rogers. I also had earle lower the manual pull stations to a maximum height of 48".
|
BLD08-02137
| FIRE-Final Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 1:58:11 PM | P | PASS |
|
|
Life safety passed.
|
BLD08-00418
| FIRE-Final Inspection | 12/4/2008 | 12/5/2008 | 12/5/2008 1:10:19 PM | A | PART |
|
|
A temporary occupancy was given with sam rogers and gordon goldsmiths permission until the missing fire hydrant is installed, in-duct detectors are installed for operation of the fire/smoke dampers, the exit discharge light is repaired at the main exit, the "Area of Refuge" sign is provided with battery backup and permanent area of refuge signs are placed. Temporary signs have been installed at this time.
|
BLD08-02284
| FIRE-Alarm Testing | 12/5/2008 | 12/5/2008 | 12/5/2008 11:46:11 AM | P | PASS |
|
|
Fire alarm testing was not required. Life safety passed.
|
BLD08-02284
| FIRE-Final Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 11:45:37 AM | P | PASS |
|
|
Life safety passed
|
FIR08-00158
| INSP-Supply line flush | 12/4/2008 | 12/5/2008 | 12/5/2008 10:40:33 AM | A | PASS |
|
|
Underground flush passed
|
FIR08-00645
| INSP-Supply line flush | 12/4/2008 | 12/5/2008 | 12/5/2008 10:40:10 AM | A | PASS |
|
|
Underground flush passed
|
BLD08-01868
| FIRE-Final Inspection | 12/5/2008 | 12/5/2008 | 12/5/2008 10:00:18 AM | P | CANC |
|
|
AJ Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|