Inspections for the day of: Monday, December 5, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02324 FIRE-Sprinkler Rough-in12/5/201112/5/201112/5/2011 5:56:46 PMPPART
Overhead fire sprinkler work as marked on approved plans to date are approved for cover.
BLD11-01556 FIRE-Final Inspection12/2/201112/5/201112/5/2011 5:46:01 PMADEFR
No fire related signatures required on this project per permit details.
BLD11-01845 FIRE-Sprinkler Rough-in12/5/201112/5/201112/5/2011 5:42:36 PMAPART
OH work at two areas approved for cover. Ref. sprinkler plans for annotations.
FIR08-00604 INSP-Alarm Testing12/2/201112/5/201112/5/2011 5:39:54 PMAPART
Completed notification testing at building 1 garage, building 2 and 3 garages including 1st -4th floors and building 4 garage. Verified previous correction items and repairs at buildings 2 and 3, record drawings for field changes finished with the exception of the first floor levels. Noted items today include one non-functional av at the 2nd floor #3 corridor, insufficient dB at resident storage bldg. #3, dB levels at the finished model units are not adequate, DH at elevator lobbies building #2 did not release. Discussed schedule and items for next test date.
BLD11-02584 FIRE-Final Inspection12/2/201112/5/201112/5/2011 12:20:28 PMAPASS
Fire life safety inspection passed.