Inspections for the day of: Friday, December 5, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01762 ELE-Aging Inspection12/5/201412/5/201412/12/2014 1:39:06 PM DONE
Waiting on owner
ELE14-03034 Electrical Rough-In12/5/201412/5/201412/5/2014 4:10:16 PMPPASS
Grid rough in ok cover
ELE14-03272 Conference12/5/201412/5/201412/5/2014 2:20:27 PMPDONE
Phone #: ###-#### Inspection requested via web by BARRY KENDALL This permit to cover only new service to interior I-line. Other interior wiring to be installed by others. Discussed NEC 250.50- Using all available grounding electrodes shall be used including fire riser underground metal piping system.
ELE14-03352 Electrical Rough-In12/4/201412/5/201412/5/2014 1:54:12 PMPPASS
please call prior to inspection, i am 20 mins out. thx mike Phone #: ###-#### Inspection requested via web by michael hunt Addition rough in ok cover
ELE14-03356 Electrical Rough-In12/5/201412/5/201412/5/2014 1:37:11 PMPPASS
New circuits from existing panel/breakers. Utility/garage wall. Existing basement wiring terminated into crawl. Thank You, Lynn Phone #: ###-#### Inspection requested via web by Lynn Solmon New washer and dryer recepticals added, No new wiring in basement just terminated old wiring. Rough in ok cover
ELE14-03034 Final12/4/201412/5/201412/5/2014 12:51:49 PMPPASS
We are requesting a final inspection for tomorrow 12/5/14 in the PM. Our onsite contact is Larry @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate Final ok
ELE13-03105 Electrical Rough-In12/4/201412/5/201412/5/2014 11:25:26 AMAPASS
Transformer secondary underground Phone #: ###-#### Inspection requested via web by matt miller Secondaries south west corner rough in ok cover
ELE14-03102 Rough-In Permanent Service12/4/201412/5/201412/5/2014 9:29:52 AMAPASS
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Unit 103 rough in ok cover
103 service p/s u/g n ok
ELE14-03165 Rough-In Permanent Service12/4/201412/5/201412/5/2014 9:26:44 AMAPASS
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Shell rough in ok cover. House service p/s u/g n ok
ELE14-03165 Electrical Rough-In12/5/201412/5/201412/5/2014 9:25:42 AMPFAIL
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor
550.16-Feed to job trailer shall have seperate grouned and grounding conductors. Bonding of trailer shall not connect to a grounded conductor.
400.5-Max over current for #6 Multi conductor cable 45 amp 50 amp breaker installed. Max over current for #8 35 amp 40 amp installed.