ELE11-02621
| ELE-Aging Inspection | 12/5/2016 | 12/5/2016 | 12/6/2016 1:13:51 PM | | DONE |
|
|
Still under construction
|
MIS16-00381
| ELE-Conference | 12/5/2016 | 12/5/2016 | 12/5/2016 1:42:27 PM | A | FAIL |
|
|
Possible work being done without permits. Any questions call Jim Storey Electrical is being done without permit, material was on site and work had been started. No one was on site
|
ELE16-02600
| Electrical Rough-In | 12/5/2016 | 12/5/2016 | 12/5/2016 1:15:32 PM | P | NR |
|
|
Dave. Garage ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Not ready
|
ELE16-03878
| Electrical Rough-In | 12/2/2016 | 12/5/2016 | 12/5/2016 9:30:59 AM | A | PASS |
|
|
Please call 30 minutes before you get there so I can meet you. Thank you. Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester Kitchen,living room, upstairs bed and bath,downstairs bath and bedroom to the east ok cover
|
ELE07-03492
| ELE-Aging Inspection | 12/5/2016 | 12/5/2016 | 12/5/2016 9:00:02 AM | | PASS |
|
|
Same as previous notes will look into it to find out what it is that is needed to be looked at.
|
ELE16-03366
| Permanent Service | 12/2/2016 | 12/5/2016 | 12/5/2016 8:35:06 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams 110.24 Available fault current calculation required prior to being energized 210.4 Multi wire branch circuits shall simultaneousl disconnect all ungrounded conductors 230.6 Burial depth not deep enough will encase in 2in concrete
|