Inspections for the day of: Tuesday, December 5, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02434 Electrical Rough-In12/5/201712/5/201712/5/2017 2:12:12 PMPPASS
I should be ready after 12:00 to have you reinspect. If you give me call I''ll make sure I''m there. Thanks for working with me on this! Phone #: ###-#### Inspection requested via web by Dennis Ahern p/s o/h rec ok
ELE17-04084 Temporary Service12/5/201712/5/201712/5/2017 1:03:08 PMPPASS
Phone #: ###-#### Inspection requested via web by danny perrine
t/s u/g n ok
ELE17-03999 Rough-In Permanent Service12/4/201712/5/201712/5/2017 11:16:07 AMAPASS
Phone #: ###-#### Inspection requested via web by danny perrine
Rough in ok cover p/s u/g n ok
ELE17-02434 Rough-In Permanent Service12/4/201712/5/201712/5/2017 11:15:53 AMAFAIL
I''m replacing my panel today and would like an inspection late in the day to make sure I get it all in. Please call ahead to confirm I am ready for inspection. Thanks! 208 841 7286. Phone #: ###-#### Conference noted on ELE17-02435. 200.6- Grounded conductors larger than #6 shall be identified with white markings at terminations points.
250.24- Grounding electrode system shall be connected to grounded conductor a main disconnecting means.
250.52- Ground rod gronding electrode system shall be supplemented by additional rod or metal piping system.
250.66- If metal underground water pipe present a minimum of #4 copper grounding electrode conductor shall connect with in 5' of entrance to crawl space.
358.30, 42- Emt Connectors shall be tight and shall be secured with in 3' of top and bottom.
ELE17-04066 Rough-In Permanent Service12/4/201712/5/201712/5/2017 10:14:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok