Inspections for the day of: Tuesday, December 5, 2017.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-05345 Final11/28/201712/5/201712/5/2017 3:39:37 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC17-05345 Pressure Test12/5/201712/5/201712/5/2017 3:39:21 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
5lb flue
MEC17-05165 Final12/4/201712/5/201712/5/2017 3:22:13 PMPFAIL
Please call 30 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
need C.O. alarms, lineset needs armaflex to coil,condencer needs to be 3ft away from gas meter, need water tight conduit,and right sized fuses
MEC17-05414 Final12/5/201712/5/201712/5/2017 3:00:10 PMPPASS
3pmish please call Joseph ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC17-05414 Pressure Test12/5/201712/5/201712/5/2017 2:59:55 PMPPASS
3pmish please call Joseph ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
20lb gas
MEC17-05446 Conference12/5/201712/5/201712/5/2017 2:34:02 PMPPASS
Please call before you go so we can have someone meet you there. Would prefer later afternoon Phone #: ###-#### Inspection requested via web by Dan McFate
MEC17-05444 Final12/5/201712/5/201712/5/2017 2:02:07 PMPPASS
PLEASE CALL OUR LEAD INSTALLER BRAD WHEN 30 MINS IN ROUTE, 3-5P THIS AFTERNOON WOULD BE BEST IF AT ALL POSSIBLE.

THANK YOU SO MUCH Phone #: ###-#### Inspection requested via web by Rick Montgomery
MEC17-04810 Rough-in12/5/201712/5/201712/5/2017 1:37:06 PMPPASS
Will Phone #: ###-####
MEC17-04809 Rough-in12/5/201712/5/201712/5/2017 1:36:37 PMPPASS
Will Phone #: ###-####
MEC17-04773 Final12/5/201712/5/201712/5/2017 12:55:51 PMPPASS
MEC17-03101 Final12/5/201712/5/201712/5/2017 11:11:16 AMAPASS
Call smoky 20 min in advamce to meet inspector at this house and open the electric gate
Thanks Phone #: ###-#### Inspection requested via web by Manuel Canto
MEC17-03954 Final12/4/201712/5/201712/5/2017 10:07:41 AMAPASS
Garage Code: 7285 Phone #: ###-#### Inspection requested via web by Jasmin Godina
MEC17-02525 Final12/4/201712/5/201712/5/2017 9:35:55 AMAFAIL
Back door will be open. Inspection requested via web by Aaron Alandt
range exaust not approved material
MEC17-04625 Rough-in12/4/201712/5/201712/5/2017 9:12:20 AMAPASS
Will Phone #: ###-####
MEC17-04807 Rough-in12/4/201712/5/201712/5/2017 9:12:05 AMAPASS
Will Phone #: ###-####
MEC17-04808 Rough-in12/4/201712/5/201712/5/2017 9:11:50 AMAPASS
Will Phone #: ###-####
MEC17-04810 Rough-in12/4/201712/5/201712/5/2017 9:09:22 AMAFAIL
Will Phone #: ###-####
romex in return plenum, dryer vent is crushed, need more hangers
MEC17-04809 Rough-in12/4/201712/5/201712/5/2017 9:08:33 AMAFAIL
Will Phone #: ###-####
all duct needs to be supported by its own hanger
MEC17-05424 Rough-in12/4/201712/5/201712/4/2017 10:25:21 AMACANC
Phone #: ###-#### >> Inspection requested via web by Jasmin Godina Inspection cancelled from web by: Jasmin Godina