FIR04-00732
| INSP-Final Inspection | 12/3/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 12/6/2004 10:19:24 AM
|
BLD04-02507
| FIRE-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | A | PASS |
|
|
Structural inspector please verify that the automatic flush bolt is repaired at the main exit. Fire life safety finaled.
|
BLD04-02516
| FIRE-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | FAIL |
|
|
Need to test the duct smoke detector and final the fire sprinkler permit 12/6/2004 2:58:02 PM
|
FIR04-00585
| INSP-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled
|
BLD04-02003
| FIRE-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | FAIL |
|
|
Provide correct hardware on two of the west facing exit doors. Provide correct light level on face of exit sign or provide another type of approved exit sign at south (west facing) exit
|
FIR04-00679
| INSP-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly
|
FIR04-00679
| INSP-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly
|
FIR04-00725
| INSP-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | FAIL |
|
|
Annual inspection tag on the riser does not have year punched out and there is no indication the anti-freeze loop has had its annual inspection
|
FIR04-00486
| INSP-Final Inspection | 12/3/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 12/6/2004 4:06:28 PM
|
BLD04-01191
| FIRE-Conference | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 12/6/2004 2:02:42 PM
|
BLD04-01191
| FIRE-Conference | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 12/6/2004 2:02:42 PM
|
BLD04-00966
| FIRE-Final Inspection | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 12/6/2004 11:02:53 AM
|
FIR04-00390
| INSP-Supply line flush | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PART |
|
|
Underground flush passed. Hydro test of the underground supply piping failed. 12/6/2004 3:26:38 PM
|
FIR04-00390
| INSP-Supply line flush | 12/6/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PART |
|
|
Underground flush passed. Hydro test of the underground supply piping failed. 12/6/2004 3:26:38 PM
|
FIR04-00631
| INSP-Conference | 12/3/2004 | 12/6/2004 | 12/6/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 12/6/2004 2:00:27 PM
|