ELE06-00711
| Electrical Rough-In | 12/5/2006 | 12/6/2006 | 12/6/2006 4:16:25 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 12/5/2006 at 1:06:17 PM. Contact: ###-####. all grid ceilings in basement ok, part for 10th floor xformers, and panels, elevator motors need abraision protection at PHeads, clearence duct over panels shall be above 6ft
|
ELE06-04341
| Rough-In Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 3:22:05 PM | P | PASS |
|
|
Thank You; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units p/s u/g new ok
|
ELE06-04340
| Rough-In Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 3:21:27 PM | P | PASS |
|
|
Thank You; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units, p/s u/g new ok
|
ELE06-04487
| Electrical Rough-In | 12/6/2006 | 12/6/2006 | 12/6/2006 3:20:02 PM | P | PART |
|
|
Cover for ground ring.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cover for engineered lighting protection system ok approved drawings will be provided, needs 24" deep all locations per drawings
|
ELE06-04388
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 2:06:47 PM | P | CANC |
|
|
concrete has been poured over conduit, inspection for cover, any questions please call Sean Dunn at ###-####; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe see added r/i
|
ELE06-04388
| Electrical Rough-In | 12/6/2006 | 12/6/2006 | 12/6/2006 2:06:25 PM | P | PART |
|
|
concrete has been poured over conduit, inspection for cover, any questions please call Sean Dunn at ###-####; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe electrode ok for dirt cover
|
ELE06-04180
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 1:04:14 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: David ok
|
ELE06-03927
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 12:39:26 PM | P | FAIL |
|
|
butch; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called corr. 410.15 shall grd all poles at hand hole
|
ELE06-03525
| Final | 12/4/2006 | 12/6/2006 | 12/6/2006 12:12:28 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/4/2006 at 11:41:12 AM. Contact: ###-####. ok
|
ELE06-04201
| Electrical Rough-In | 12/5/2006 | 12/6/2006 | 12/6/2006 11:09:45 AM | A | PART |
|
|
Underground cover inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs u/g ok contr will secure permit for ground ring installation a outfit from canada and the excavator was installing it no cover for grd ring u/g ok only
|
ELE06-03480
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 10:38:55 AM | P | CANC |
|
|
Fadil; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt Inspection cancelled from web by: Cathy Weisshaupt
|
ELE06-02835
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 10:38:11 AM | A | FAIL |
|
|
wayne ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith fee due corr. called left message 680.43(B) lights over hot tub shall be be of type noted by 680.43(B)(1) (c) 1& 2
|
ELE06-03583
| Final | 12/4/2006 | 12/6/2006 | 12/6/2006 10:18:41 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/4/2006 at 2:15:25 PM. Contact: ###-####. ok
|
ELE06-03334
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 9:36:53 AM | A | PASS |
|
|
Please call ###-#### with problems or questions. Thank You. Internet Inspection Request from: Latisha Peltier ok
|
ELE06-04396
| Rough-In Permanent Service | 12/5/2006 | 12/6/2006 | 12/6/2006 9:12:16 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton corr. called 250.66 &104(A)(1) needs #4 copper to bond water, 250.24(A)(5) remove bond screw at subpanel and water bond
|
ELE06-04396
| Electrical Rough-In | 12/6/2006 | 12/6/2006 | 12/6/2006 9:09:59 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton u/g ok only
|
ELE06-04482
| Conference | 12/5/2006 | 12/6/2006 | 12/6/2006 8:30:46 AM | A | DONE |
|
|
craig =cell ###-#### call 1st before insp
|
ELE06-04482
| Electrical Rough-In | 12/6/2006 | 12/6/2006 | 12/6/2006 8:30:33 AM | A | PASS |
|
|
craig =cell ###-#### call 1st before insp
ok floor heat told owner needs to make sure sensor wire does not overlap other wires
|