Inspections for the day of: Wednesday, December 6, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00711 Electrical Rough-In12/5/200612/6/200612/6/2006 4:16:25 PMPPART
Scheduled by a contractor via Hello! on 12/5/2006 at 1:06:17 PM. Contact: ###-####. all grid ceilings in basement ok,
part for 10th floor xformers, and panels, elevator motors need abraision protection at PHeads, clearence duct over panels shall be above 6ft
ELE06-04341 Rough-In Permanent Service12/6/200612/6/200612/6/2006 3:22:05 PMPPASS
Thank You; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
r/i all 4 units p/s u/g new ok
ELE06-04340 Rough-In Permanent Service12/6/200612/6/200612/6/2006 3:21:27 PMPPASS
Thank You; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
r/i all 4 units, p/s u/g new ok
ELE06-04487 Electrical Rough-In12/6/200612/6/200612/6/2006 3:20:02 PMPPART
Cover for ground ring.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cover for engineered lighting protection system ok approved drawings will be provided, needs 24" deep all locations per drawings
ELE06-04388 Final12/6/200612/6/200612/6/2006 2:06:47 PMPCANC
concrete has been poured over conduit, inspection for cover, any questions please call Sean Dunn at ###-####; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe see added r/i
ELE06-04388 Electrical Rough-In12/6/200612/6/200612/6/2006 2:06:25 PMPPART
concrete has been poured over conduit, inspection for cover, any questions please call Sean Dunn at ###-####; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe electrode ok for dirt cover
ELE06-04180 Final12/6/200612/6/200612/6/2006 1:04:14 PMPPASS
Phone #: ###-#### Internet Inspection Request from: David ok
ELE06-03927 Final12/6/200612/6/200612/6/2006 12:39:26 PMPFAIL
butch; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
called corr. 410.15 shall grd all poles at hand hole
ELE06-03525 Final12/4/200612/6/200612/6/2006 12:12:28 PMPPASS
Scheduled by a contractor via Hello! on 12/4/2006 at 11:41:12 AM. Contact: ###-####. ok
ELE06-04201 Electrical Rough-In12/5/200612/6/200612/6/2006 11:09:45 AMAPART
Underground cover inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs u/g ok contr will secure permit for ground ring installation a outfit from canada and the excavator was installing it no cover for grd ring u/g ok only
ELE06-03480 Final12/6/200612/6/200612/6/2006 10:38:55 AMPCANC
Fadil; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt Inspection cancelled from web by: Cathy Weisshaupt
ELE06-02835 Final12/5/200612/6/200612/6/2006 10:38:11 AMAFAIL
wayne ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
fee due corr. called left message 680.43(B) lights over hot tub shall be be of type noted by 680.43(B)(1) (c) 1& 2
ELE06-03583 Final12/4/200612/6/200612/6/2006 10:18:41 AMAPASS
Scheduled by a contractor via Hello! on 12/4/2006 at 2:15:25 PM. Contact: ###-####. ok
ELE06-03334 Final12/5/200612/6/200612/6/2006 9:36:53 AMAPASS
Please call ###-#### with problems or questions. Thank You. Internet Inspection Request from: Latisha Peltier ok
ELE06-04396 Rough-In Permanent Service12/5/200612/6/200612/6/2006 9:12:16 AMAFAIL

Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton
corr. called 250.66 &104(A)(1) needs #4 copper to bond water, 250.24(A)(5) remove bond screw at subpanel and water bond
ELE06-04396 Electrical Rough-In12/6/200612/6/200612/6/2006 9:09:59 AMAPART

Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton
u/g ok only
ELE06-04482 Conference12/5/200612/6/200612/6/2006 8:30:46 AMADONE
craig =cell ###-#### call 1st before insp
ELE06-04482 Electrical Rough-In12/6/200612/6/200612/6/2006 8:30:33 AMAPASS
craig =cell ###-#### call 1st before insp

ok floor heat told owner needs to make sure sensor wire does not overlap other wires