ELE06-02178
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 4:36:48 PM | P | CANC |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see conference
|
ELE06-02178
| Conference | 12/6/2006 | 12/6/2006 | 12/6/2006 4:36:22 PM | P | DONE |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith explained to contr that he has to have a separate permit for each meter
|
ELE06-03880
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 3:40:10 PM | P | CANC |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see rip, wrong type request
|
ELE06-03880
| Rough-In Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 3:39:29 PM | P | PASS |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover ceiling, p/s, exst meter pak, n, ok
|
ELE06-03424
| Final | 12/6/2006 | 12/6/2006 | 12/6/2006 3:01:13 PM | P | PASS |
|
|
damon - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-03761
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 2:16:45 PM | A | PASS |
|
|
Jack I Finally got building permit and need a meter for power. meter labled around back soon as we get power you can come in and do a final Thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s , exst meter pak n ok
|
ELE06-04155
| Final | 12/4/2006 | 12/6/2006 | 12/6/2006 1:16:41 PM | P | FAIL |
|
|
READY FOR A FINAL INSPECTION FOR THIS PROJECT, ANY QUESTIONS PLEASE CONTACT US AT THE SHOP.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called left message, left corr notice, nec 408.4 circuit directory shall be completed, 110.16 hazard signs shall be installed for arc flash, 110.26(F)(1) there shall be no ducts in dedicated panel space, 408.38 panelboards shall be deadfront, Note: floor is flooded, need to see when dry for other possible corrections
|
ELE06-04481
| Temporary Service | 12/6/2006 | 12/6/2006 | 12/6/2006 12:43:14 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok
|
ELE06-03738
| Temporary Service | 12/6/2006 | 12/6/2006 | 12/6/2006 12:29:26 PM | P | NR |
|
|
DEEON - HE IS ON SITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail met elect, told to call after gec installed
|
ELE06-04291
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:16:33 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no tlr
|
ELE06-04292
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:16:02 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord
|
ELE06-04293
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:15:15 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no tlr
|
ELE06-04294
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:14:45 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, cord on tlr, no entry
|
ELE06-04294
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 11:14:05 AM | P | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n ok
|
ELE06-04295
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:13:26 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, cord on tlr, no entry
|
ELE06-04295
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 11:12:52 AM | P | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n ok
|
ELE06-04296
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:11:22 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final cord on tlr, no tlr entry
|
ELE06-04296
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 11:10:46 AM | P | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n ok
|
ELE06-04297
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:10:11 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final no cord
|
ELE06-04302
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:09:35 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord
|
ELE06-04298
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:09:03 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, cord on tlr, no entry
|
ELE06-04298
| Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 11:08:29 AM | P | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n ok
|
ELE06-04300
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:07:31 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no tlr
|
ELE06-04299
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:06:59 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord end
|
ELE06-04284
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:06:22 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord
|
ELE06-04286
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:05:47 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final left sticker, cord on tlr, no trailer entry
|
ELE06-04287
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:01:38 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord
|
ELE06-04289
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 11:00:50 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, meter and cord 12-4-06 per 312
|
ELE06-04290
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 10:59:25 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no cord set
|
ELE06-04276
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 10:56:14 AM | A | PASS |
|
|
bud; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, no trailer
|
ELE06-02148
| Final | 12/5/2006 | 12/6/2006 | 12/6/2006 8:59:29 AM | A | PASS |
|
|
mitch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-03928
| Permanent Service | 12/5/2006 | 12/6/2006 | 12/6/2006 8:32:59 AM | A | PASS |
|
|
kevin - call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h n (rec) ok
|
ELE06-04010
| Electrical Rough-In | 12/5/2006 | 12/6/2006 | 12/6/2006 8:15:36 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 12/5/2006 at 2:56:45 PM. Contact: ###-####. ok to cover clg
|
ELE06-04463
| Electrical Rough-In | 12/5/2006 | 12/6/2006 | 12/6/2006 8:14:26 AM | A | PASS |
|
|
Pole base insection on street lights; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz bases ok, told contr to address project and to provide erosion control sign
|
ELE06-03427
| Conference | 12/6/2006 | 12/6/2006 | 12/6/2006 8:14:13 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 12/6/2006 at 7:13:53 AM. Contact: ###-####. Inspection cancelled from web by: Jamie Winters
|