Inspections for the day of: Wednesday, December 6, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00628 INSP-Final Inspection12/5/200612/6/200612/6/2006 4:19:42 PMPFAIL
Still need the alarm connections tested. Need two additional tamper switches for the anti-freeze loop backflow preventor per IFC 903.4.1, need forward flush, head wrench, backflow certification, trapeze calcs and wall to deck in the warehouse as per the previous inspection entry.
FIR06-00937 INSP-Final Inspection12/5/200612/6/200612/6/2006 4:03:20 PMAPASS
The hod suppression system operated correctly. Dave hanniman approved the locationo of the manual pull station. If it was to be relocated to meet IMC it would be in a public area.
FIR06-00850 INSP-Sprinkler Rough-in/Hydro12/6/200612/6/200612/6/2006 3:51:48 PMPPASS
sprinkler piping is ok to cover
FIR05-00836 INSP-Final Inspection12/6/200612/6/200612/6/2006 2:30:36 PMAFAIL
See the city approved plans for the pharmacy for devices tested. All of the notification devices have been tested. See the approved plans for locateions where a 15 and a 75 need swapped. I stopped the inspection due to time constraints and upon finding a duct smoke detector missing the plug in the sample tube and it shut the smoke damper. Also multiple smoke detectors still had tape on them and a/v's still had tape and paper covering them or were missing covers. I found one junction box at the failed duct detector that was missing its cover and had wiring spilling from it. I found one manual pull station at the east exit that was not attached to the wall.
MIS06-00327 FIR-Final12/5/200612/6/200612/6/2006 2:14:07 PMAPART
A temporary occupancy was given until the door hardware is corrected and emergency lights are added. See correction notice for specific areas.
FIR06-00338 INSP-Final Inspection12/5/200612/6/200612/6/2006 1:43:50 PMAFAIL
The resubmitted plans were not on site. One pendant head is blocked by a light fixture. Underground flush and testing of the flow switch passed.
FIR06-00318 INSP-Final Inspection12/5/200612/6/200612/6/2006 1:42:04 PMAFAIL
See the plans for locaions of of lighting obstructions and being located too close to a supply register. Also need to know the size of the water meter