Inspections for the day of: Thursday, December 6, 2007.
Number of inspections: 28
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00450 FIRE-Final Inspection12/6/200712/6/200712/7/2007 8:02:27 AMPFAIL
Pending completion of items 4, 5,and 12 per IFC 2003 section 509 regarding the fire command center.
BLD06-03304 FIRE-Final Inspection12/6/200712/6/200712/7/2007 7:58:41 AMPNR
Final pending shell permit.
BLD06-03291 FIRE-Final Inspection12/6/200712/6/200712/7/2007 7:58:08 AMPNR
Final pending shell permit.
FIR07-00960 INSP-Final Inspection12/6/200712/6/200712/6/2007 3:49:24 PMPPASS
Kitchen system passed. KR
BLD07-01082 FIRE-Final Inspection12/6/200712/6/200712/6/2007 3:25:44 PMPFAIL
Need project related fire sprinkler permit issued and requested for inspection, also pending shell and core life safety finals, noted corridor needs to be clear of storage and obstructions, doors on self closers must not be blocked open.
FIR07-00027 INSP-Final Inspection12/6/200712/6/200712/6/2007 3:21:41 PMPPASS
As-built plans provided, fire sprinkler permit finaled.
FIR07-00031 INSP-Final Inspection12/6/200712/6/200712/6/2007 3:20:31 PMPPASS
Accepted as-built plans, permit finaled.
FIR07-00022 INSP-Final Inspection12/6/200712/6/200712/6/2007 3:18:57 PMPPASS
As-builts accepted, fire sprinkler permit finaled.
FIR07-00333 INSP-Alarm Testing12/6/200712/6/200712/6/2007 3:17:51 PMPPASS
Final pending NFPA 72 forms.
FIR07-00334 INSP-Alarm Testing12/6/200712/6/200712/6/2007 3:17:09 PMPPASS
Inspection passed, final pending NFPA 72 forms.
FIR07-00676 INSP-Alarm Testing12/6/200712/6/200712/6/2007 3:16:20 PMPPASS
Corrections verified for completion, fire alarm testing passed.
BLD06-03309 FIRE-Final Inspection12/6/200712/6/200712/6/2007 3:15:05 PMPNR
Need FA permit final and shell and core BLD permit approvals.
FIR07-00129 INSP-Final Inspection12/6/200712/6/200712/6/2007 3:13:56 PMPPASS
Shell and core fire alarm permit passed final inspection, as-built documentation to be delivered as discussed.
FIR07-00923 INSP-Sprinkler Rough-in12/5/200712/6/200712/6/2007 3:12:16 PMPPART
Rough-in is approved pending area separation at two locations as discussed and red-lined on approved plans.
FIR06-00674 INSP-Final Inspection12/6/200712/6/200712/6/2007 1:51:07 PMPPASS
UG fire supply line permit finaled.
FIR07-00860 INSP-Final Inspection12/6/200712/6/200712/6/2007 1:38:58 PMPPART
Fire sprinkler work is acceptable for phase 1 only of the permit scope.
FIR07-00868 INSP-Final Inspection12/6/200712/6/200712/6/2007 1:37:31 PMPPASS
Fire sprinkler permit finaled.
FIR06-00727 INSP-Sprinkler Rough-in/Hydro12/5/200712/6/200712/6/2007 1:30:59 PMAPART
OH is approved for cover at the drop ceilings on the 2nd, 3rd and 4th floor common corridors only, noted one missing drop and hanger restraint at the 3rd floor corridor-can be verifed at next inspeciton.
BLD07-01432 FIRE-Final Inspection12/6/200712/6/200712/6/2007 11:47:24 AMPPASS
Fire life safety passed. KR
FIR07-00701 INSP-Final Inspection12/6/200712/6/200712/6/2007 11:43:20 AMPPASS
Sprinkler permit passed, corrections were made per Troy Cobbleys notes..KR
FIR07-00778 INSP-Final Inspection12/5/200712/6/200712/6/2007 11:33:58 AMAPASS
Fire passed, for ths permit number..KR
FIR07-00515 FIR-Aging Inspection12/6/200712/6/200712/6/2007 10:49:34 AM DEFR
Construction in progress.
FIR07-00897 INSP-Sprinkler Rough-in12/5/200712/6/200712/6/2007 10:35:35 AMAPART
UG fire supply line is approved for cover.
FIR07-00803 INSP-Final Inspection12/4/200712/6/200712/6/2007 10:04:57 AMAFAIL
Missing caps at the FDC, need to remove the allen wrench from the flow switch at the main riser and replace the cover ASAP, provide a current annual inspection for the existing system, need resubmitted plans available on site at the next inspection.
FIR07-00699 INSP-Final Inspection12/5/200712/6/200712/6/2007 9:59:15 AMAFAIL
Need to provide fire alarm notification at two conference rooms (these rooms are indicated on plans as "office"), provide cover plates at two locations where pull stations have been moved, adjust the fire door at the elevator for complete closure, will verify new nac at next inspection, the south corridor manaul pull and the remainder of devices tested okay.
FIR07-00719 INSP-Final Inspection12/5/200712/6/200712/6/2007 9:53:18 AMAFAIL
Missing one required notification device at the 1st floor corridor north side-see approved plans for annotations, the manual pull station and remainder of devices tested okay, will verify new nac panel at next inspection.
BLD07-01536 FIRE-Final Inspection12/5/200712/6/200712/6/2007 8:55:58 AMAPASS
Fire life safety passed. KR
BLD07-01535 FIRE-Final Inspection12/5/200712/6/200712/6/2007 8:55:15 AMAPASS
Fire life safety passed