Inspections for the day of: Monday, December 6, 2010.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00088 FIR-Aging Inspection12/6/201012/6/201012/8/2010 2:16:45 PM FAIL
Requires fire alarm interconnect.
FIR02-00268 FIR-Aging Inspection12/6/201012/6/201012/8/2010 2:11:32 PM FAIL
Ref. previous correction notice items.
FIR10-00355 INSP-Sprinkler Rough-in12/6/201012/6/201012/6/2010 5:10:25 PMPFAIL
Rough-in inspection for the 1st floor completed- Noted exposed combustible construction lacking coverage at the open area south end, need to maintain 130 ft2 max spacing at the kitchen, field modifications in branchline routing at the east entry vestibule need to be installed per plan or proved by new calcs as five heads are now fed from a single 1" outlet. See redline areas on plan set for locations. Note: okay to cover remainder of installation.
FIR10-00495 INSP-Sprinkler Rough-in12/6/201012/6/201012/6/2010 4:58:15 PMPPART
Need stamped approved plans on site, discussed hydro testing, soffit obstructions etc.
BLD10-02103 FIRE-Final Inspection12/6/201012/6/201012/6/2010 3:48:23 PMPPASS
Correction items field verified for completion, fire life safety passed. Final hardware install at the east exit to be verified at structural final inspection as agreed.
BLD10-02764 FIRE-Final Inspection12/6/201012/6/201012/6/2010 3:44:48 PMPFAIL
See correction notice and permit documents on site for list of items including: post signage at the main entry/exit, provide approved door hardware at the main exit, post fire extinguisher as discussed, repair exposed electrical wiring at the storage closet light fixture.