FIR06-00088
| FIR-Aging Inspection | 12/6/2010 | 12/6/2010 | 12/8/2010 2:16:45 PM | | FAIL |
|
|
Requires fire alarm interconnect.
|
FIR02-00268
| FIR-Aging Inspection | 12/6/2010 | 12/6/2010 | 12/8/2010 2:11:32 PM | | FAIL |
|
|
Ref. previous correction notice items.
|
FIR10-00355
| INSP-Sprinkler Rough-in | 12/6/2010 | 12/6/2010 | 12/6/2010 5:10:25 PM | P | FAIL |
|
|
Rough-in inspection for the 1st floor completed- Noted exposed combustible construction lacking coverage at the open area south end, need to maintain 130 ft2 max spacing at the kitchen, field modifications in branchline routing at the east entry vestibule need to be installed per plan or proved by new calcs as five heads are now fed from a single 1" outlet. See redline areas on plan set for locations. Note: okay to cover remainder of installation.
|
FIR10-00495
| INSP-Sprinkler Rough-in | 12/6/2010 | 12/6/2010 | 12/6/2010 4:58:15 PM | P | PART |
|
|
Need stamped approved plans on site, discussed hydro testing, soffit obstructions etc.
|
BLD10-02103
| FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 3:48:23 PM | P | PASS |
|
|
Correction items field verified for completion, fire life safety passed. Final hardware install at the east exit to be verified at structural final inspection as agreed.
|
BLD10-02764
| FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 3:44:48 PM | P | FAIL |
|
|
See correction notice and permit documents on site for list of items including: post signage at the main entry/exit, provide approved door hardware at the main exit, post fire extinguisher as discussed, repair exposed electrical wiring at the storage closet light fixture.
|