FIR06-00254
| INSP-Conference | 11/24/2010 | 12/1/2010 | | A | |
|
|
Follow up inspection. Steve Bevans ###-####
|
FIR05-00021
| FIR-Aging Inspection | 12/6/2010 | 12/6/2010 | 12/7/2010 2:25:23 PM | | NR |
|
|
Taylor Brothers is supposedly working on getting these permits finaled.
|
BLD10-02086
| FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 3:44:38 PM | P | PASS |
|
|
life safety passed
|
FIR08-00143
| INSP-Alarm Testing | 12/6/2010 | 12/6/2010 | 12/6/2010 3:32:40 PM | P | FAIL |
|
|
Provide city approved drawings and a flashing hat in the elevator car when the shaft and machine room detector is activated.
|
FIR09-00109
| INSP-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 3:23:08 PM | P | PASS |
|
|
permit finaled
|
FIR08-00367
| FIR-Aging Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 2:38:48 PM | | NR |
|
|
wip
|
FIR10-00525
| INSP-Sprinkler Rough-in | 12/6/2010 | 12/6/2010 | 12/6/2010 2:32:05 PM | P | FAIL |
|
|
The wrong upright sprinkler heads have been installed. The attice heads appear to be overspaced from the wall, in the attic, at the south end of the attic. The pendant heads in three bathrooms are not providing sprinkler coverage in the shower areas. The transition from 1 1/4" pipe to 1 1/2" pipe is in the wrong location. The additional elbows installed in the wet system are ok per tim. Todays inspection was just for the new south addition and not for any of the existing interior work.
|
BLD10-00114
| FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 1:32:51 PM | P | FAIL |
|
|
Remove all thumbturn locks and provide single action hardware, install all panic hardware as shown, provide signage on doors 30 aand 31, provide fire extinguishers as discussed, provide one hour rating for the fire riser room, mount the address numbers, provide and mount the occupant load signs, provide exit sign/emergency light/exit discharge lights as per plan, verfiy the change in door hardware with Carl for doors 14 and 21.
|
BLD10-00988
| FIRE-Final Inspection | 12/3/2010 | 12/6/2010 | 12/6/2010 1:07:02 PM | A | FAIL |
|
|
Provide indicator at the keyed hardware on the main exit door, repire the inactive leaf locking hardware on the double doors to the service bay and provide "No parking fire lane " signs as discussed.
|
FIR10-00406
| INSP-Alarm Testing | 12/3/2010 | 12/6/2010 | 12/6/2010 12:38:31 PM | A | PASS |
|
|
Permit finaled
|
BLD10-02316
| FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 12:35:59 PM | P | PASS |
|
|
Life safety passed. The thumbturn lock was removed from the rear exit door as I waited and the exit sign was repaired.
|
FIR10-00611
| INSP-Final Inspection | 12/3/2010 | 12/6/2010 | 12/6/2010 12:33:00 PM | A | PASS |
|
|
Permit finaled
|
FIR10-00598
| INSP-Final Inspection | 12/3/2010 | 12/6/2010 | 12/6/2010 12:32:23 PM | A | PASS |
|
|
Permit finaled. The hood suppression system functinos correctly. Mark approved the location of the manual pull.
|