Inspections for the day of: Monday, December 6, 2010.
Number of inspections: 13
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00254 INSP-Conference11/24/201012/1/2010 A 
Follow up inspection. Steve Bevans ###-####
FIR05-00021 FIR-Aging Inspection12/6/201012/6/201012/7/2010 2:25:23 PM NR
Taylor Brothers is supposedly working on getting these permits finaled.
BLD10-02086 FIRE-Final Inspection12/6/201012/6/201012/6/2010 3:44:38 PMPPASS
life safety passed
FIR08-00143 INSP-Alarm Testing12/6/201012/6/201012/6/2010 3:32:40 PMPFAIL
Provide city approved drawings and a flashing hat in the elevator car when the shaft and machine room detector is activated.
FIR09-00109 INSP-Final Inspection12/6/201012/6/201012/6/2010 3:23:08 PMPPASS
permit finaled
FIR08-00367 FIR-Aging Inspection12/6/201012/6/201012/6/2010 2:38:48 PM NR
wip
FIR10-00525 INSP-Sprinkler Rough-in12/6/201012/6/201012/6/2010 2:32:05 PMPFAIL
The wrong upright sprinkler heads have been installed. The attice heads appear to be overspaced from the wall, in the attic, at the south end of the attic. The pendant heads in three bathrooms are not providing sprinkler coverage in the shower areas. The transition from 1 1/4" pipe to 1 1/2" pipe is in the wrong location. The additional elbows installed in the wet system are ok per tim. Todays inspection was just for the new south addition and not for any of the existing interior work.
BLD10-00114 FIRE-Final Inspection12/6/201012/6/201012/6/2010 1:32:51 PMPFAIL
Remove all thumbturn locks and provide single action hardware, install all panic hardware as shown, provide signage on doors 30 aand 31, provide fire extinguishers as discussed, provide one hour rating for the fire riser room, mount the address numbers, provide and mount the occupant load signs, provide exit sign/emergency light/exit discharge lights as per plan, verfiy the change in door hardware with Carl for doors 14 and 21.
BLD10-00988 FIRE-Final Inspection12/3/201012/6/201012/6/2010 1:07:02 PMAFAIL
Provide indicator at the keyed hardware on the main exit door, repire the inactive leaf locking hardware on the double doors to the service bay and provide "No parking fire lane " signs as discussed.
FIR10-00406 INSP-Alarm Testing12/3/201012/6/201012/6/2010 12:38:31 PMAPASS
Permit finaled
BLD10-02316 FIRE-Final Inspection12/6/201012/6/201012/6/2010 12:35:59 PMPPASS
Life safety passed. The thumbturn lock was removed from the rear exit door as I waited and the exit sign was repaired.
FIR10-00611 INSP-Final Inspection12/3/201012/6/201012/6/2010 12:33:00 PMAPASS
Permit finaled
FIR10-00598 INSP-Final Inspection12/3/201012/6/201012/6/2010 12:32:23 PMAPASS
Permit finaled. The hood suppression system functinos correctly. Mark approved the location of the manual pull.