Inspections for the day of: Thursday, December 6, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01992 FIRE-Final Inspection12/6/201212/6/201212/6/2012 3:46:57 PMPPASS
Life safety passed
FIR12-00664 INSP-Final Inspection12/6/201212/6/201212/6/2012 2:58:42 PMPFAIL
Waiting for approval to pass from TIm Frost due to new hydraulic calculations being required due to the racking/storage in the cooler.
FIR12-00664 INSP-Sprinkler Rough-in12/6/201212/6/201212/6/2012 2:56:25 PMPPASS
Rough-in passed
FIR12-00106 INSP-Final Inspection12/6/201212/6/201212/6/2012 2:28:40 PMPPASS
Permit finaled
FIR12-00106 INSP-Sprinkler Rough-in/Hydro12/6/201212/6/201212/6/2012 2:27:53 PMPPASS
Permit finaled. Underground flush passed.
FIR12-00163 INSP-Sprinkler Rough-in/Hydro12/6/201212/6/201212/6/2012 2:27:21 PMPPART
Not all of the branchline restraints have been installed as indicated on the city approved plans. Also the 2" riser nipples are shown at 1'-8 1/2" in height but actually measure just over 3'-0" and the riser nipple piping at nodes 14 and 15 as well as being taller, has a 1'-0" offset with an additional 2" elbow. Plans/hydraulic calculations need to be resubmitted for review due to the safety margin being nearly exceeded. All other items appear ok. The forward flush of the backflow easily passed.
FIR12-00619 INSP-Sprinkler Rough-in12/6/201212/6/201212/6/2012 1:41:59 PMPPASS
Sprinkler piping is ok to cover.
FIR12-00620 INSP-Sprinkler Rough-in12/6/201212/6/201212/6/2012 1:41:40 PMPPASS
Sprinkler piping is ok to cover.
BLD12-00550 FIRE-Final Inspection12/6/201212/6/201212/6/2012 1:36:36 PMPPASS
life safety passed
BLD12-01992 FIRE-Final Inspection12/5/201212/6/201212/6/2012 11:40:33 AMAFAIL
Provide fire extinguisher as discussed and per the fire review comments.
FIR12-00591 INSP-Final Inspection12/3/201212/6/201212/6/2012 10:36:30 AMAFAIL
No actual inspection was performed based on Review Note #1 which states that if there are changes/additions beyond the red lined notes on the drawings and comments in the review notes then Plan Modifications are required. Per the electricians comments and his plans, many additions were required. I noted that the actual floor plan does not match the approved drawings or the as-builts the contractor had on site. There are additional rooms not shown on the plans and these rooms do not have smoke detector coverage or notification appliances as required for the design on this project. Since I was already at the project we went ahead and set off the alarms and I measured the sound levels in the "sound booths" and verified that the minumum sound level was met.
FIR12-00582 INSP-Sprinkler Rough-in/Hydro12/5/201212/6/201212/6/2012 9:46:27 AMAPASS
See the city approved plans for the remaining three underground supply lines that are ok to cover.
FIR12-00537 INSP-Final Inspection12/4/201212/6/201212/6/2012 9:44:43 AMAPASS
Permit finaled
BLD12-02450 FIRE-Final Inspection11/30/201212/6/201212/6/2012 9:44:11 AMAPASS
Life safety passed