BLD12-01992
| FIRE-Final Inspection | 12/6/2012 | 12/6/2012 | 12/6/2012 3:46:57 PM | P | PASS |
|
|
Life safety passed
|
FIR12-00664
| INSP-Final Inspection | 12/6/2012 | 12/6/2012 | 12/6/2012 2:58:42 PM | P | FAIL |
|
|
Waiting for approval to pass from TIm Frost due to new hydraulic calculations being required due to the racking/storage in the cooler.
|
FIR12-00664
| INSP-Sprinkler Rough-in | 12/6/2012 | 12/6/2012 | 12/6/2012 2:56:25 PM | P | PASS |
|
|
Rough-in passed
|
FIR12-00106
| INSP-Final Inspection | 12/6/2012 | 12/6/2012 | 12/6/2012 2:28:40 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00106
| INSP-Sprinkler Rough-in/Hydro | 12/6/2012 | 12/6/2012 | 12/6/2012 2:27:53 PM | P | PASS |
|
|
Permit finaled. Underground flush passed.
|
FIR12-00163
| INSP-Sprinkler Rough-in/Hydro | 12/6/2012 | 12/6/2012 | 12/6/2012 2:27:21 PM | P | PART |
|
|
Not all of the branchline restraints have been installed as indicated on the city approved plans. Also the 2" riser nipples are shown at 1'-8 1/2" in height but actually measure just over 3'-0" and the riser nipple piping at nodes 14 and 15 as well as being taller, has a 1'-0" offset with an additional 2" elbow. Plans/hydraulic calculations need to be resubmitted for review due to the safety margin being nearly exceeded. All other items appear ok. The forward flush of the backflow easily passed.
|
FIR12-00619
| INSP-Sprinkler Rough-in | 12/6/2012 | 12/6/2012 | 12/6/2012 1:41:59 PM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
FIR12-00620
| INSP-Sprinkler Rough-in | 12/6/2012 | 12/6/2012 | 12/6/2012 1:41:40 PM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD12-00550
| FIRE-Final Inspection | 12/6/2012 | 12/6/2012 | 12/6/2012 1:36:36 PM | P | PASS |
|
|
life safety passed
|
BLD12-01992
| FIRE-Final Inspection | 12/5/2012 | 12/6/2012 | 12/6/2012 11:40:33 AM | A | FAIL |
|
|
Provide fire extinguisher as discussed and per the fire review comments.
|
FIR12-00591
| INSP-Final Inspection | 12/3/2012 | 12/6/2012 | 12/6/2012 10:36:30 AM | A | FAIL |
|
|
No actual inspection was performed based on Review Note #1 which states that if there are changes/additions beyond the red lined notes on the drawings and comments in the review notes then Plan Modifications are required. Per the electricians comments and his plans, many additions were required. I noted that the actual floor plan does not match the approved drawings or the as-builts the contractor had on site. There are additional rooms not shown on the plans and these rooms do not have smoke detector coverage or notification appliances as required for the design on this project. Since I was already at the project we went ahead and set off the alarms and I measured the sound levels in the "sound booths" and verified that the minumum sound level was met.
|
FIR12-00582
| INSP-Sprinkler Rough-in/Hydro | 12/5/2012 | 12/6/2012 | 12/6/2012 9:46:27 AM | A | PASS |
|
|
See the city approved plans for the remaining three underground supply lines that are ok to cover.
|
FIR12-00537
| INSP-Final Inspection | 12/4/2012 | 12/6/2012 | 12/6/2012 9:44:43 AM | A | PASS |
|
|
Permit finaled
|
BLD12-02450
| FIRE-Final Inspection | 11/30/2012 | 12/6/2012 | 12/6/2012 9:44:11 AM | A | PASS |
|
|
Life safety passed
|