Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01214 ELE-Aging Inspection12/6/201712/6/201712/13/2017 10:46:53 AM CANC
Too busy
ELE10-01426 ELE-Aging Inspection12/6/201712/6/201712/13/2017 10:46:08 AM CANC
Too busy
ELE10-01638 ELE-Aging Inspection12/6/201712/6/201712/13/2017 10:45:51 AM CANC
Too busy
ELE17-01032 Electrical Rough-In12/6/201712/6/201712/6/2017 2:27:18 PMPPASS
Rough-in inspection for cover in Units 320, 322, 323, 324, 326, 328, 420, 423
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas as noted on inspection request and noted on prints ok to cover
ELE17-04060 Permanent Service12/4/201712/6/201712/6/2017 2:04:51 PMPFAIL
Corbin ###-#### Perm. Service and 2 outlets. Inspect Bldg F 204 or 201 Phone #: ###-#### Inspection requested via web by Samatha Solberg
OCPD device needed for sub panel
ELE17-01702 Final12/5/201712/6/201712/6/2017 1:28:21 PMPPASS
Final Re-Inspection Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Corrections fixed final ok
ELE17-04100 Temporary Service12/5/201712/6/201712/6/2017 1:27:58 PMPCANC
Phone #: ###-#### Inspection requested via web by Emmet Bushman
ELE17-02307 Electrical Rough-In12/6/201712/6/201712/6/2017 11:23:43 AMPPASS
Garage and mood room inspection. Phone #: ###-#### Inspection requested via web by Garrett Collins
Garage and mood/mud room ok to cover
ELE17-04079 Permanent Service12/6/201712/6/201712/6/2017 11:23:16 AMPPASS
Contact is Todd Sellman. Please call when heading over so he can meet with inspector please. Phone #: ###-#### Inspection requested via web by Todd Sellman
p/s o/h n ok
ELE17-04095 Temporary Service12/5/201712/6/201712/6/2017 11:22:42 AMAPASS
Please inspect temp pole. Thanks!! ?? Phone #: ###-#### Inspection requested via web by Robert Schroder
t/s u/g n ok
ELE17-03778 Electrical Rough-In12/5/201712/6/201712/6/2017 10:08:00 AMAPASS
Underground inspection call cody for questions Phone #: ###-#### Inspection requested via web by Shane Lott
Phase 4 underground and switch gear extension of conduit ok to cover
ELE17-04058 Final12/5/201712/6/201712/6/2017 9:43:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat
Seperate permit will be pulled for work in warehouse.
Occupancy card signed, Final ok.
ELE17-01733 Final12/5/201712/6/201712/6/2017 9:28:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Christy Cheney
corrections fixed Final ok
ELE17-02905 Final12/5/201712/6/201712/6/2017 9:20:18 AMANH
Robert Phone #: ###-####
Nobody home
ELE17-03159 Final12/5/201712/6/201712/6/2017 9:13:33 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brandon Blackham
210.12 AFCI protection required for all bedrooms(AFCI in-op)
ELE17-03944 Final12/1/201712/6/201712/6/2017 8:50:51 AMAPASS
TML will have a ladder on site for roof access. Phone #: ###-#### Inspection requested via web by sam petterson
Final ok