Inspections for the day of: Wednesday, December 6, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00476 FIRE-Final Inspection12/5/201712/6/201712/6/2017 2:05:51 PMAPASS
Life fire safety inspection for this permit passed/complete.
BLD17-00472 FIRE-Final Inspection12/5/201712/6/201712/6/2017 2:05:30 PMAPASS
Life fire safety inspection for this permit passed/complete.
BLD17-00470 FIRE-Final Inspection12/5/201712/6/201712/6/2017 2:05:08 PMAPASS
Life fire safety inspection for this permit passed/complete.
FIR17-00678 INSP-Sprinkler Rough-in12/5/201712/6/201712/6/2017 11:25:58 AMAPASS
Rough to ocver inspection for area of work complete, area of work approved for cover. A fire sprinkler head will need to be added in the entry of the mens restroom, no fire sprinkler head at time of inspection (this area is out of the scope of work but is part of the tenant space). Fire sprinkler head will need to be added to pass life fire safety inspection at project completion.
BLD17-03798 FIRE-Final Inspection12/5/201712/6/201712/6/2017 11:04:15 AMAFAIL
Tried to call point of contact, Jeff Phone #: ###-####, phone number provided was not for point of contact. Went to space to see if it was open, space was locked with no access, life fire safety inspection will need to be rescheduled.
FIR17-00267 INSP-Sprinkler Rough-in12/5/201712/6/201712/6/2017 10:47:10 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on level 5 east of room 511 complete, rooms east of 511 on level 5 approved for cover with exception to room 512, room 512 will be inspected at a later date.
FIR17-00393 INSP-Sprinkler Rough-in/Hydro12/5/201712/6/201712/6/2017 10:28:17 AMAFAIL
Overhead fire sprinkler system lost 3 pounds in an hour and a half, overhead will need to be re-hydro tested.
FIR17-00623 INSP-Final Inspection12/5/201712/6/201712/6/2017 10:18:00 AMAPART
Partial final inspection complete for fire sprinklers in area of work passed/complete. Northwest corridor (part of core and shell) has dry type fire sprinkler heads that are supplied from the coffee shop side, dry heads to be installed before coffee shop completion. Dry sprinkler head piping install will be verified at life fire safety inspection.
FIR17-00655 INSP-Final Inspection12/6/201712/6/201712/6/2017 10:14:15 AMAPART
Final inspection for fire alarms in area of work passed/complete. Fire alarm permit will remain in issued status until core and shell is complete.
FIR17-00665 INSP-Final Inspection12/6/201712/6/201712/6/2017 10:12:22 AMACANC
FIR17-00655 INSP-Alarm Testing12/5/201712/6/201712/6/2017 10:11:11 AMADONE
Fire alarm testing complete.
FIR17-00649 INSP-Final Inspection12/4/201712/6/201712/5/2017 12:41:47 PMPCANC
Inspecting Technician: Ray McQueen Building Access: open 0900 - 1900 Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson