FIR19-00892
| INSP-Sprinkler Rough-in | 12/6/2019 | 12/6/2019 | 12/6/2019 2:28:15 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, scope of work approved for cover.
Print on counter to left of entry lock box code 3266 Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-00294
| FIRE-Final Inspection | 12/5/2019 | 12/6/2019 | 12/6/2019 1:26:26 PM | A | NR |
|
|
A stated in th 05DEC entry: Not ready for final life fire safety inspection, FIR19-00913 is for the in duct smoke detectors, FIR permit needs to scheduled, inspected and finaled before life fire safety will be completed. It is cooridnated to be completed the morning of 09DEC2019.
Nate Phone #: ###-####
|
BLD19-01312
| FIRE-Final Inspection | 12/6/2019 | 12/6/2019 | 12/6/2019 1:24:47 PM | P | FAIL |
|
|
Fire alarm panel has open circuit trouble on NAC circuit, panel needs to be normal for life fire safety inspection. A fire alarm vendor will need to be present for the life fire safety inspection, due to fire alarm devices being removed and re-installed during this scope of work a fire alarm test will be required to verify proper operation of fire alarm system in scope of work areas.
Tom Phone #: ###-####
|
FIR19-00562
| INSP-Final Inspection | 12/6/2019 | 12/6/2019 | 12/6/2019 1:17:02 PM | P | PASS |
|
|
Final fire sprinkler inspection for scope of work is complete.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00152
| INSP-Final Inspection | 12/6/2019 | 12/6/2019 | 12/6/2019 1:15:29 PM | P | PASS |
|
|
Final inspection for AES communicator complete.
|
FIR18-00152
| INSP-Alarm Testing | 12/6/2019 | 12/6/2019 | 12/6/2019 1:14:38 PM | P | PASS |
|
|
AES testing complete.
Please call Kevin Brubaker Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
FIR19-00672
| INSP-Final Inspection | 12/5/2019 | 12/6/2019 | 12/6/2019 11:11:53 AM | A | CANC |
|
|
Point of contact not available when inspection could be completed, inspection request will need to be rescheduled, this request is cancelled.
Gabe is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00846
| INSP-Sprinkler Rough-in | 12/5/2019 | 12/6/2019 | 12/6/2019 10:34:12 AM | A | PASS |
|
|
Rough to cover inspection for area of work complete, 3 hangers to be relocated due to incorrect install, hangers are in prep/employee only area, north side above ceiling grid. Will verify hanger correction during next inspection request, cover is approved.
Contact Fred Silva ###-#### 30 min prior to RTC Insp. start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00766
| INSP-Conference | 12/5/2019 | 12/6/2019 | 12/6/2019 9:48:26 AM | A | DONE |
|
|
Fire conference is complete.
Contact Ken Orahood 08-###-#### 30 min prior to Conf Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD17-03344
| FIRE-Final Inspection | 12/5/2019 | 12/6/2019 | 12/6/2019 9:18:16 AM | A | PASS |
|
|
Final life fire safety inspection is complete.
Jason Phone #: ###-####
|
FIR18-00858
| INSP-Final Inspection | 12/4/2019 | 12/6/2019 | 12/6/2019 9:17:24 AM | A | PART |
|
|
Walk through complete for levels 4, 5 and 6, notated city approved plans with red ink for corrections.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|